MYCOMFORT LARGE
P09,P11 = 3
The contact status indicates that the unit is in cooling mode.
P09,P11 = 4
The contact status indicates that the unit is in heating mode.
P09,P11 = 5
The contact status indicates if the control in ON or OFF
P09,P11 = 6
The contact status indicates if an alarm is triggered (serious or non-serious, see
"Alarms")
P09,P11 = 7
The contact is used to switch ON/OFF any external device for dehumidifying the air
(cooling mode only). The ON/OFF logic is based on a reading of the humidity in the
room and the SETPOINT selected with parameter P13. It follows the diagram shown:
P09,P11 = 8
The contact is used to switch ON/OFF any external device for humidifying the air
(heating mode only). The ON/OFF logic is based on a reading of the humidity in the
room and the SETPOINT selected with parameter P13. It follows the diagram shown:
P09,P11 = 9
The status of the contact indicates whether the air temperature is too high compared
to the temperature SETPOINT (only in the "summer" mode); the ON/OFF logic is thus
tied to the value of the temperature SETPOINT, according to the following step:
P09,P11 = 10
The status of the contact indicates whether the air temperature is too low compared
to the temperature SETPOINT (only in the "winter" mode); the ON/OFF logic is thus
tied to the value of the temperature SETPOINT, according to the following step:
P09,P11 = 11
The digital output is not governed by the controller; the contact is always open.
P09,P11 = 12
The contact status indicates that water temperature is low. The activation/deactivation
logic follows the step:
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
The two tables below provide a detailed explanation of the meaning of the contact
associated with each digital output:
Air humidity
Air humidity
Air temperature
Air temperature
Water temperatu-
re
39
DIGITAL 1 OUTPUT
P10 = 0 (NO
contact)
OPEN
CLOSED
contact
contact
P09
--
--
0
Not used
SUMME
WINTER WINTER
1
Operating mode
R
Unit in cooling or
NO
YES
2
heating mode
Unit in cooling
NO
YES
3
mode
Unit in heating
NO
YES
4
mode
OFF
ON
5
Controller status
NO
YES
6
Alarm triggered
External
dehumidification
NO
YES
7
call
External
NO
YES
8
humidification call
High room
NO
YES
9
temperature
Low room
NO
YES
10
temperature
--
--
11
Not used
Low water
YES
NO
12
temperature
DIGITAL 2 OUTPUT
P12 = 0 (NO
contact)
OPEN
CLOSED
contact
contact
P11
--
--
0
WINTER WINTER SUMME
SUMME
1
Operating mode
R
Unit in cooling or
NO
YES
2
heating mode
Unit in cooling
NO
YES
3
mode
Unit in heating
NO
YES
4
mode
OFF
ON
5
Controller status
NO
YES
6
Alarm triggered
External
NO
YES
dehumidification
7
call
External
NO
YES
8
humidification call
High room
NO
YES
9
temperature
Low room
NO
YES
10
temperature
Water circuit
YES
NO
11
enabled for cooling
Water circuit
YES
NO
12
enabled for heating
P10 = 1 (NC
contact)
OPEN
CLOSED
contact
contact
GB
--
--
SUMME
R
YES
NO
YES
NO
YES
NO
ON
OFF
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
--
--
NO
YES
P12 = 1 (NC
contact)
OPEN
CLOSED
contact
contact
--
--
R
YES
NO
YES
NO
YES
NO
ON
OFF
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
NO
YES
NO
YES
FC66002638 - rev. 05