Galletti MYCOMFORT LARGE Manual Del Usuario página 47

Mando lcd para terminales
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 94
MYCOMFORT LARGE
SERIOUS ALARMS
Alarm code
-
Code 01 = error of external air temperature sensor (in case of on-board
thermostat)
-
Code 02 = error of internal air temperature sensor (in case of wall mounted
thermostat and disconnected external air temperature sensor)
NON-SERIOUS ALARMS
THERMOSTAT OFF
THERMOSTAT ON
-
Code 03 = water sensor error
-
Code 04 = external humidity probe error (only if a remote temperature sensor
is installed)
-
Code 05 = internal humidity probe error
NB: the alarm code is displayed only when the thermostat is switched off
MODBUS
The protocol implemented in the controller is Modbus RTU (9600, N, 8, 2) on RS485
FUNCTIONS IMPLEMENTED
0x03 : Read Holding Registers
0x04 : Read Input Registers
0x10 : Write Multiple registers
EXCEPTIONS IMPLEMENTED
Exception Code 02: Invalidate data address
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
LIST OF SUPERVISION PARAMETERS
ADDRESS
REGISTER
0
Status
1
Speed
2
Air temperature
3
Humidity
4
Water temperature
5
P00: Configuration
6
P05: DIN Config.
7
T. Active setpoint
8
T. User setpoint
9
LCD version
1 0
P09: DOUT1 Config.
1 1
P10: DOUT1 Logic
1 2
P11: DOUT2 Config.
1 3
P12: DOUT2 Logic
1 4
P14: AOUT1/2 Config.
1 5
Analog output 1
1 6
Analog output 2
5 0
Digital 1
5 1
Hourly programming
5 2
Setpoint - Cooling
5 3
Setpoint - Heating
5 4
Minimum Setpoint – Cool. R/W
5 5
Maximum Setpoint – Cool. R/W
5 6
Minimum Setpoint – Heat. R/W
5 7
Maximum Setpoint – Heat. R/W
5 8
Speed
5 9
Economy Correction
6 0
Modulating fan mode
Description of read-only registers [R]
-
"Status" Register
> On/Off: unit status (0: Off, 1=On)
> S/W: operation mode (0: S=cooling, 1:W=heating);
> P01: "on unit/wall-mounted" parameter
> Eco: Economy logic active
> Min.T: Minimum Temperature logic selected
> Alarm: general alarm indication (activated when any of the managed alarms is
triggered)
> Vc status of digital output Vc
> Vh: status of digital output Vh
> DI1: logical value of dig. input 1 (the physical status of the input depends on the
associated logic)
> DI2: logical value of dig. input 2 (the physical status of the input depends on the
associated logic)
> P07: "DIN 2 Logic" parameter
> P06: "DIN 1 Logic" parameter
> Dehum: dehumidification ON (0:no, 1:yes)
> P04: "water probe present" parameter
> DOUT1: Digital Input 1 status
> DOUT2: Digital Input 2 status
-
"Speed" Register: current operating speed of the indoor unit
47
TYPE
U.O.M.
R
-
R
-
R
[°C/10]
R
%
R
[°C/10]
R
-
R
-
R
[°C/10]
R
[°C/10]
R
-
R
R
R
R
R
R
[%]
R
[%]
R/W
-
R/W
-
R/W
[°C/10]
R/W
[°C/10]
[°C/10]
[°C/10]
[°C/10]
[°C/10]
R/W
-
R/W
[°C/10]
R/W
-
FC66002638 - rev. 05
GB

Publicidad

Tabla de contenido
loading

Tabla de contenido