Siemens SIMATIC S7-1500 Manual De Usuario página 24

Ocultar thumbs Ver también para SIMATIC S7-1500:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 53
External partner
S7 Engineering (external)
TIA Portal, STEP 7
S7 HMI (external)
SIMATIC Panel
WinCC RT Advanced V15.1
WinCC RT Professional V15.1
WinCC V7 V7.4 Service Packs
WinCC flexible
S7 SIMATIC NET OPC (external)
SIMATIC NET V14 and higher
S7 communication to SIMATIC
controllers (external)
S7-1200 Controller
S7-1500 Controller
S7-1500 Software Controller
S7-300 Controller
S7-400 Controller
WinAC
S7 communication to third-party
applications (external)
Other libraries for various high-
level languages (e.g. LibNoDave)
24
Special features
Can be configured over any Windows Ethernet interface
Special features
Configuration in STEP 7 including connection configuration (S7 routed connection)
Configuration in STEP 7 including connection configuration (S7 routed connection)
Configuration in STEP 7 including connection configuration (S7 routed connection)
see application example
(https://support.industry.siemens.com/cs/ww/en/view/109750290)
Via unspecified connection
Requirement
You have enabled "PUT/GET".
Addressing
IP address: Windows interface in use
Rack = 0; slot = index
Special features
Configuration in STEP 7 including connection configuration (S7 connection)
Special features
Configuration in STEP 7 including connection configuration (add S7 routed
connection)
Configuration in STEP 7 including connection configuration (add S7 routed
connection)
Configuration in STEP 7 including connection configuration (add S7 routed
connection)
Not supported
Not supported
Not supported
Special features
Supported communication methods
Data access to non-optimized data
Requirement
You have enabled "PUT/GET".
The index of the CPU is 1.
Addressing of the external partner via the CPU
Not supported
Addressing the CPU via the external partner
IP address: IP address of one of the Windows Ethernet interfaces
Port number: 102
Rack = 0, slot = set index = 1
Add-ons to CPU 1505SP (F/T/TF), CPU 1507S (F), CPU 1508S (F) Version 2.6
A5E45929273-AD, 07/2019

Publicidad

Tabla de contenido
loading

Tabla de contenido