Any partner
Passive TCP/IP connection
With an TCP/IP connection where you are only receiving and not sending data, you will not be informed about a loss of
connection.
26
Special features
Via PC communication interface
Supported communication methods
TCP programmed
UDP programmed
Note: Secure OUC communication is not possible over the PC communication
interface.
Addressing of the external partner via the CPU
HW ID: 59 (PC communication interface)
IP address: IP address of the external partner
Port number: As defined
Addressing the CPU via external partner
IP address: IP address of the connected Windows Ethernet interfaces
Port number: As defined
Via runtime communication interface
Supported communication methods
TCP programmed
UDP programmed
ISOonTCP programmed
With IP Routing or NAT Routing set up under Windows
Addressing of the external partner via the CPU
HW ID: 0
IP address: IP address of the external partner
Port number: As defined
Addressing the CPU via external partner
IP address: Runtime communication interface
Port number: As defined
With port forwarding set up under Windows
Addressing of the external partner via the CPU
HW ID: 0
IP address: IP address of the Siemens RT-VMM network adapter
Port number: As defined
Addressing the CPU via external partner
IP address: IP address of the connected Windows Ethernet interfaces
Port number: As defined
Add-ons to CPU 1505SP (F/T/TF), CPU 1507S (F), CPU 1508S (F) Version 2.6