SIMATIC IPC427E / IPC477E (PRO)
If you are using a SIMATIC Microbox PC supported by the CPU, note the following reference information for your device:
Property
Hardware version
IPC427E: FS ≥ AA
IPC477E: FS ≥ AA
BIOS version
V21.01.11
Operating systems
Graphics driver
Version for Windows 7:
Version for Windows 10:
Available on supplied USB flash drive with
version 04/2018.
LED use
IPC427E: Supported, configurable
IPC477E (PRO): Not supported
NVRAM use
Supported, 135 KB can be used for user data
Mass storage
Using onboard interfaces for PROFINET or PROFIBUS:
PN / IE (LAN) X1
Not supported
PN / IE (LAN) X2
Yes
PN / IE (LAN) X3
Yes
CPU Power Level
Set the CPU Power Level to "Determinism optimized".
Special features
Use with Microsoft Windows Embedded Standard 7
When you use the PC station on the IPC with the "Microsoft Windows Embedded Standard 7" operating system, install the
Windows update for universal C RunTime in Windows from the Microsoft Support website
US/download/details.aspx?id=49077).
Windows reboot
To use the Windows reboot on the SIMATIC IPC427E / IPC477E, assign the Ethernet interfaces X2 or X3 to the PC station
in STEP 7.
Instruction "SHUT_DOWN: Shut down target system"
To reboot Windows via Remote Desktop on the SIMATIC IPC477E, also use the "-f" parameter with the Shutdown
instruction for immediate shutdown.
Add-ons to CPU 1505SP (F/T/TF), CPU 1507S (F), CPU 1508S (F) Version 2.6
A5E45929273-AD, 07/2019
Windows Embedded Standard 7 E SP1 (32-
bit or 64-bit)
Windows Embedded Standard 7 P SP1 (64-
bit)
Windows 7 Ultimate (32-bit or 64-bit)
Windows 10 Enterprise LTSB 2016 (64-bit)
32-bit: 15.45.21.4821
64-bit: 15.45.21.64.4821
15.46.05.64.4771
Notes
The hardware version can be found on the
rating plate of your SIMATIC IPC.
Operation with Windows 7 Ultimate and
Windows 10 requires a Windows installation in
Legacy mode. Win 10 Legacy boot handling
(https://support.industry.siemens.com/cs/ww/en/
view/109749498)
If you did not receive a USB flash drive with the
SIMATIC IPC, contact Customer Support.
Operating system installation on CFast (internal
or external) < 16 GB
(https://www.microsoft.com/en-
31

Publicidad

Tabla de contenido
loading

Tabla de contenido