Commissioning
1. Before commissioning, ensure that all connections of the PE 6 are correctly
carried out.
2. Apply the compressed air to the system.
3. Check that the switch outputs are functioning properly.
7
Operation
Vacuum switch pressures too high
The vacuum switch has only been designed for operation with vacuums (referring
to atmosphere). Pressures up to 5 bar do not cause damage to the switch;
however, pressures from 2 bar may adversely affect precision and service life.
O Observe the maximum permissible pressure values on the rating plate and in
the technical data.
When switching inductive loads, use a recovery diode on the load!
Setting switching points (pressure and vacuum switch)
Depending on the PE 6 variant used,
W
one switching point with fixed hysteresis or
W
two switching points can be set.
Switching points are set via the teach button (2) (see
Outputs 1 and 2 operate independently of each other.
One switching point with fixed hysteresis
1. Press button (2) for approx. 2 s until both LEDs flash alternately.
2. Press button (2) until the LED of the desired output lights up.
3. Apply the vacuum/pressure for the desired teach point.
4. Press button (2) for approx. 2 s to set the teach point. The LED will flash.
– Vacuum switch:
Switch-on point (SP) = teach point (TP) - 20% of TP
(Example: TP = -700 bar, SP = -560 mbar)
Fixed hysteresis (2% F.S. = 20 mbar)
– Pressure switch:
Switch-on point (SP) = teach point (TP) -5% of TP
(Example: TP = 6 bar, SP = 5.7 bar)
Fixed hysteresis (2% F.S. = 200 mbar)
5. Repeat the process from step 1 for the second output.
Two switching points
6
1. Press button (2) for approx. 2 s until both LEDs flash alternately.
2. Press button (2) until the LED of the desired output lights up.
3. Apply the vacuum/pressure for the desired switch-on/switch-off point.
4. Press button (2) for approx. 2 s to set the first switching point (the sequence of
switching points is freely selectable).
The LED will flash.
5. Apply the vacuum/pressure for the desired switch-off/switch-on point.
6. Press button (2) for approx. 2 s to set the second switching point.
7. Repeat the process from step 1 for the second output.
Resetting to factory settings
1. Disconnect the PE 6 from the operating voltage.
2. Hold down the (2) button and apply the operating voltage.
Both LEDs will flash.
3. Press button (2) for approx. 2 s until both LEDs go out.
Factory settings
Teach
Output
Vacuum switch
points
1
1
SP = -600 mbar
2
SP = -300 mbar
2
1
SP = -750 mbar, rP = -600 mbar SP = 0.5 bar, rP = 0.3 bar
2
SP = -550 mbar, rP = -500 mbar SP = 0.5 bar, rP = 0.3 bar
CAUTION
1
).
5
Pressure switch
SP = 1 bar
SP = 1 bar
8
Maintenance
The PE 6 is maintenance-free. Please contact the service department at AVENTICS if
you have any technical problems.
9
Cleaning and servicing
Solvents and aggressive cleaning agents
Solvents and aggressive cleaning agents could damage the PE 6.
O Only use water for cleaning and, if necessary, kerosene or benzine.
How to clean the PE 6:
1. Make sure that all relevant system parts are not under voltage or pressure.
2. Clean the PE 6.
10 Disposal
O Dispose of the PE 6 in accordance with the applicable national regulations.

11 Technical data

PE 6
Vacuum switch
Sensor type
Measuring medium
Medium
Compressed air in accordance with ISO 8573-1:2010
(max. particle size: 40
Pressure range
Operating voltage
10 – 30 VDC, protective extra-low voltage (PELV in
accordance with IEC 364-4-41), residual ripple (P-P) max.
Switch output
2x PNP, NO ("make" contact), max. 200 mA
Hysteresis
1 switching point: 2% F.S., 2 switching points: adjustable
Protective circuit
Operating voltage protected against polarity reversal,
Repetitive precision
Temperature
3% of full scale in the operating temperature range
influence
Electrical connection
Measuring medium
connection
Protection class
Insulating resistance
Testing voltage
Interference emission
Tested in accordance with EN 61000-6-3:2007
Interference immunity
Tested in accordance with EN 61000-6-2:2005
Switching times
Current consumption
Temperature ranges
Operation: 0 to +60 °C, medium: 0 to +50 °C,
Permissible humidity
10 to 90% rel. humidity without condensation or ice
Resistance to
overpressure
Weight
1) When switching inductive loads, use a corresponding recovery diode on the load.
2) Max. cable length: 30 m
3) 100,000 cycles < 1 s
CAUTION
Pressure switch
Piezo-resistive
Non-aggressive gases, dry air
m; pressure dew point: ≤ 3 °C;
μ
3
oil content: max. 1 mg/m
-1 to 0 bar
0 to 10 bar
10%
switch output is short circuit-proof, timed
1% of full scale
Push-in fitting, M8x1, 4-pin
Flange plate 2x M2.5
IP40 (according to EN 60529/IEC 529)
>100 M at 500 VDC
1000 VDC, 1 min
< 2 ms
< 20 mA
storage: -25 to +80 °C
formation
5 bar
15 bar
Approx. 6 g