Wilo Control EC-Booster Instrucciones De Instalación Y Funcionamiento página 58

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 993
en
com
3
230
380
400
3~ 50/60 Hz
1~ 50/60 Hz
Fig. 6: Mains connection Wilo-Control EC-B
1.../EC-B 2...
2
3
PE
3~ 50/60 Hz
1~ 50/60 Hz
Fig. 7: Mains connection Wilo-Control EC-B 3...
6.5.4
Switchgear mains connection:
Control ECe-Booster
58
Installation
1
Terminal strip: Mains connection
2
1
2
Mains voltage adjustment
3
Terminal strip: Earth (PE)
Mains connection 1~230 V:
▪ Cable: 3-core
▪ Wire: L, N, PE
▪ Mains voltage adjustment: Converter bridge 230/COM
L1 L2
L3
Mains connection 3~230 V:
▪ Cable: 4-core
▪ Wire: L1, L2, L3, PE
▪ Mains voltage adjustment: Converter bridge 230/COM
Mains connection 3~380 V:
L
N
▪ Cable: 4-core
▪ Wire: L1, L2, L3, PE
▪ Mains voltage adjustment: Converter bridge 380/COM
Mains connection 3~400 V:
▪ Cable: 4-core
▪ Wire: L1, L2, L3, PE
▪ Mains voltage adjustment: Converter bridge 400/COM (factory setting)
Insert the connection cable laid by the customer through the threaded cable glands and
secure. Connect the wires to the main switch as per the connection diagram.
L1
L2
L3
1
Main switch
2
Mains voltage adjustment
1 ON
1
0
3
Terminal strip: Earth (PE)
OFF
Mains connection 1~230 V:
▪ Cable: 3-core
T1
T2
T3
▪ Wire: L, N, PE
▪ Mains voltage adjustment: Converter bridge 230/COM
Mains connection 3~230 V:
▪ Cable: 4-core
L1
L2
L3
▪ Wire: L1, L2, L3, PE
▪ Mains voltage adjustment: Converter bridge 230/COM
Mains connection 3~380 V:
▪ Cable: 4-core
L
N
▪ Wire: L1, L2, L3, PE
▪ Mains voltage adjustment: Converter bridge 380/COM
Mains connection 3~400 V:
▪ Cable: 4-core
▪ Wire: L1, L2, L3, PE
▪ Mains voltage adjustment: Converter bridge 400/COM (factory setting)
CAUTION
Risk of material damage due to incorrectly set mains voltage!
The switchgear can be operated at different mains voltages. However, the control
voltage must always be 230 V. For this reason, the cable jumper is set to the correct
mains voltage at the factory. Do not change the cable jumper! If the wrong mains
voltage is set, the controls will be destroyed!
NOTICE
Neutral conductor required
A neutral conductor is required at the mains connection for the correct functioning
of the controls.
Insert the connection cable laid by the customer through the threaded cable glands and
secure. Connect the wires to the main switch as per the connection diagram.
WILO SE 2019-07

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Control ece-booster

Tabla de contenido