Installation and operating instructions Wilo-Control EC/ECe-Booster
Commissioning
Menu no.
5.43
Description
"Pump kick" running time
Value range
0 ... 60 s
Factory setting
5 s
Menu no.
5.45
Behaviour during sensor fault – number of pumps to be
Description
switched on
Value range
0 ... 3*
Factory setting
0
* Maximum value dependent on number of pumps set
Explanation
(Menu 5.02).
Menu no.
5.46 (Control ECe-Booster only)
Description
Minimum speed of the pumps
Value range
0 ... 50 %
Factory setting
30 %
Menu no.
5.47 (Control ECe-Booster only)
Description
Maximum pump speed
Value range
80 ... 100 %
Factory setting
100 %
Menu no.
5.48 (Control ECe-Booster only)
Description
Acceleration ramp for frequency converter
Value range
0 ... 10 s
Factory setting
3 s
Menu no.
5.49 (Control ECe-Booster only)
Description
Deceleration ramp for frequency converter
Value range
0 ... 10 s
Factory setting
3 s
Menu no.
5.58
Description
Collective run signal (SBM) function
Value range
on, run
Factory setting
run
"on": switchgear ready for operation
Explanation
"Run": At least one pump is running.