Commissioning
Menu 1: Values for switching on and off
Menu no.
1.01
Description
Pressure setpoint
Value range
0.1 ... 25.0* bar
Factory setting
4 bar
* The maximum value is dependent on the set measure-
Explanation
ment range of the pressure sensor (Menu 5.11).
Menu no.
1.04
Activation threshold of the pump in % of the pressure set-
Description
point
Value range
75 ... 99 %
Factory setting
95 %
Menu no.
1.07
Base-load pump deactivation threshold in % of pressure
Description
setpoint
Value range
101 ... 125 %
Factory setting
115 %
Menu no.
1.08 (Control EC-Booster only)
Peak-load pump deactivation threshold in % of pressure
Description
setpoint
Value range
101 ... 125 %
Factory setting
110 %
Menu no.
1.09
Description
Base-load pump switch-off delay
Value range
0 ... 180 s
Factory setting
10 s
Menu no.
1.10
Description
Peak-load pump activation delay
Value range
0 ... 30 s
Factory setting
3 s
Menu no.
1.11
Description
Peak-load pump switch-off delay
Value range
0 ... 30 s
Factory setting
3 s