Quick Setup

WARNING: It is essential to check settings during the process itself, and confirm
that they are correct, before regular operation commences.
Note: After adjusting values, download data to the device, then go to View – Display to track
the effects.
Initial setup can be carried out prior to mounting into the process, but it is extremely important
to calibrate the unit and adjust the sensitivity on the product itself.
Adjust 0 % application range setting
Application
General
Dry solids
applications
Low viscosity liquids
Demanding
Hygroscopic/Wet solids
applications
High viscosity and high
conductivity liquids
Interface
Liquid A/Liquid B
detection
Foam/Liquid
1.
Open the menu View – Display and select the tab Transducer Block: Discrete Input
(Part 1). Make a note of the Sensor Value (digits).
2.
Enter the sensor value in the parameter view field: > Input > Transducer Block: Discrete
Input > Range of Application> 0%.
Adjust 100 % application range setting
Application
General applications
Demanding
applications
Interface detection
1.
Open the menu View – Display and select the tab Transducer Block: Discrete Input
(Part 1). Make a note of the Sensor Value (digits).
2.
Enter the sensor value in the parameter view field: > Input > Transducer Block: Discrete
Input > Range of Application > 100%.
Page EN-18
Pointek CLS300 (PROFIBUS PA) – QUICK START MANUAL
Material
Material
Dry solids
Low viscosity liquids
Hygroscopic/Wet solids
High viscosity and high
conductivity liquids
Liquid A/Liquid B
Foam/Liquid
Setup conditions
Sensor uncovered and a minimum of 100 mm (4")
free space all around.
Sensor immersed and then uncovered, but
retaining as much build up of material as possible
on the sensor.
Immerse the sensor in the material that has the
lowest dielectric constant.
Setup conditions
Sensor fully covered.
Sensor fully covered.
Immerse the sensor in the material that
has the highest dielectric constant.
7ML19985QF81