Switch Point adjustment
1.
Define the application range (see table on page 18).
2.
Open the menu View–Display, and select the tab Transducer Block: Discrete Input
(Part 1) to view the actual Sensor Value, the Sensor Value Discrete, the actual valid
Switch Point, and Hysteresis.
3.
Go to Input > Transducer Block: Discrete Input > Switch behavior.
- Edit the value of Switch Point 1 (default 75%).
- Edit the value of Switch Point 2 (default 25%) to adjust the Hysteresis.
Delay
• Rise Time (Off to On) determines the delay of the signal flow from the moment the sensor
becomes covered until the Primary Value is set.
• Fall Time (On to Off) determines the delay of the signal flow from the moment the sensor
becomes uncovered until the Primary Value is reset.
The delay timers have a range of values from 0.0 to 100.0 seconds.
• Go to Input > Transducer Block: Discrete Input > Delay > Rise Time (Off to On) and set the
value from 0 to 100 seconds.
• Go to Fall Time (On to Off) and set the value from 0 to 100 seconds.
If the sensor status changes before the delay interval is complete, the timer is reset to
Note:
its initial value and restarted.
Inversion
When Inversion Output = On, the level status undergoes a logical inversion.
• Go to Output > Function Block: Discrete Input > Inversion Output > Off or On
Failsafe Mode
Go to Output > Function Block: Discrete Input > Fail Safe Mode > Fail Safe Mode and select
one of the three options:
Failsafe Mode
The default value is used as the output
value.
Store the last valid output value.
The calculated output value is incorrect.
Resetting
Open the Device Menu Master Reset and select one of the three options:
Factory Reset (Restart/cold startup)
Recreates the delivery status. It resets most parameters to the factory setting.
7ML19985QF81
Pointek CLS300 (PROFIBUS PA) – QUICK START MANUAL
Description
The predefined preset safety value is output (status code
U_075).
The last valid output value is output (status code U_071).
The bad output value is accompanied by the status which
the Transducer block assigns to it (B_0xx).
Page EN-19