Before starting, complete the following:

1. Verify that the generator is OFF.
2. Set the generator main circuit breaker to OFF or
OPEN.
3. Turn off all breakers that will be powered by the
generator.
4. Check the engine crankcase oil level and, if
necessary, fill to the dipstick FULL mark with the
recommended oil. Do not fill above the FULL mark.
5. Check the fuel supply. Gaseous fuel lines must
have been properly purged and leak tested in
accordance with applicable fuel-gas codes. All fuel
shutoff valves in the fuel supply lines must be
open.
During initial start up only, the generator may exceed the
normal number of start attempts and experience an
"OVERCRANK" fault. This is due to accumulated air in
the fuel system during installation. Reset the control
Use UP and DOWN
Power Up Unit
arrows to select fuel
type then press
"ENTER"
FIRMWARE V 1.01
HARDWARE V 1.05
Fuel Selection
+ NG or LP -
ENTER
Cold Smart Start?
YES or NO
Note: If language was previously programmed this goes directly to "Select Hour"
Language
+ English -
Defaults to English
+ Espanol -
if not selected.
+ Francais -
+ Portuguese -
ENTER
Select Hour (0-23)
ENTER
- 14 +
*
* Holding the Up or Down arrow
button for 2 seconds will speed dial
through the selections
Install Wizard
ENTER
Set Exercise
Owner's Manual for 60 Hz Synergy Generator™
Install Wizard
ESC
Cold Smart Start?
- YES or NO +
Select Min (0-59)
ENTER
- 0 +
*
Select Frequency
ENTER
- WEEKLY +
- BIWEEKLY +
- MONTHLY +
Figure 7-2. Installation Wizard Menu Map
board by pushing the OFF button and ENTER key, and
restart up to two more times if necessary. If unit fails to
start, contact an Independent Authorized Service Dealer
for assistance.
Check Manual Transfer Switch
Operation
Refer to the "Manual Transfer Operation" section of the
Owner's Manual for procedures.
Electrocution. Do not manually transfer under load.
Disconnect transfer switch from all power sources
prior to manual transfer. Failure to do so will result
in death or serious injury, and equipment damage.
Select Month (1-12)
ENTER
Select Date (1-31)
- 2 +
*
Select Hour (0-23)
ENTER
- 14 +
*
ENTER
Switched to "OFF"
Hours of Protection
0 (H)
Control Panel/Start-up/Testing
DANGER
+
UP ARROW =
-
DOWN ARROW =
ENTER
Select Year (0-99)
- 13 +
- 13 +
*
Select Min (0-59)
ENTER
- 0 +
- Wednesday +
*
SYSTEM
DATE/TIME
BAT-
SUB MENUS
(000132)
*
Select Day
*
000622
29

Publicidad

Tabla de contenido
loading

Tabla de contenido