Quick Reference Guide

To clear an active alarm, press the ENTER button twice and then press AUTO. If the alarm reoccurs, contact an
Independent Authorized Service Dealer.
Table 8-4. Quick Reference Guide
Active Alarm
LED
NONE
GREEN
HIGH
RED
TEMPERATURE
OVERLOAD
RED
REMOVE LOAD
RPM SENSE LOSS
RED
NOT ACTIVATED
NONE
NONE
GREEN
LOW OIL
RED
PRESSURE
RPM SENSE LOSS
RED
OVERCRANK
RED
LOW VOLTS
RED
REMOVE LOAD
FUSE PROBLEM
RED
OVERSPEED
RED
Owner's Manual for 60 Hz Synergy Generator™
Problem
Unit running in AUTO but
Check MLCB.
no power in house.
Unit shuts down during
Check the LED's /
operation.
Screen for alarms.
Unit shuts down during
Check the LED's /
operation.
Screen for alarms.
Unit was running and
Check the LED's /
shuts down, attempts to
Screen for alarms.
restart.
Unit will not start in
See if screen says unit
AUTO with utility loss.
not activated.
Unit will not start in
Check screen for start
AUTO with utility loss.
delay countdown.
Unit will not start in
Check the LED's /
AUTO with utility loss.
Screen for alarms.
Unit will not start in
Check the LED's /
AUTO with utility loss.
Screen for alarms.
Unit will not start in
Check the LED's /
AUTO with utility loss.
Screen for alarms.
Unit will not start in
Check the LED's /
AUTO with utility loss.
Screen for alarms.
Unit will not start in
Check the LED's /
AUTO with utility loss.
Screen for alarms.
Unit will not start in
Check the LED's /
AUTO with utility loss.
Screen for alarms.
Troubleshooting / Quick Reference Guide
Things to Check
Check if the MLCB is in the ON position. If
it is in the ON position, contact an
Independent Authorized Servicing Dealer.
Check ventilation around the generator,
intake, exhaust and rear of generator. If no
obstruction, contact an Independent
Authorized Servicing Dealer.
Clear alarm and remove household loads
from the generator. Put back in AUTO and
restart.
Clear alarm and remove household loads
from the generator. Put back in AUTO and
restart. If generator does not start, contact
an Independent Authorized Servicing
Dealer.
Refer to activation section in Owner's
Manual.
If the startup delay is greater than
expected, contact an Independent
Authorized Servicing Dealer to adjust from
2 to 1500 seconds.
Check oil level and add oil per Owners
Manual. If oil level is correct, contact
Independent Authorized Servicing Dealer.
Clear alarm. Using the control panel, check
the battery by navigating to the BATTERY
MENU option from the MAIN MENU. If it
states battery is GOOD, contact an
Independent Authorized Servicing Dealer.
If it states CHECK BATTERY, replace the
battery.
Check if fuel line shutoff valve is in the ON
position. Clear alarm. Attempt to start the
unit in MANUAL. If it does not start or starts
and runs rough, contact an Independent
Authorized Servicing Dealer.
Clear alarm and remove household loads
from the generator. Put back in AUTO and
restart.
Check the 7.5amp fuse. If it is bad, replace
it with an ATO 7.5Amp fuse, if not, contact
an an Independent Authorized Servicing
Dealer.
Contact an Independent Authorized
Servicing Dealer.
Solution
37