4)
The equipment is certified for use in an ambient temperature range of –40 °C to 80 °C.
5)
The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
6)
Installation and inspection of this equipment shall be carried out by suitably trained and
authorized personnel in accordance with the applicable code of practice.
7)
The equipment shall be installed such that the supply cable is protected from mechanical
damage. The cable shall not be subjected to tension or torque. The equipment
manufacturer is not responsible for providing the supply cable.
8)
Repair of this equipment shall be carried out by suitably trained and authorized personnel
in accordance with the applicable code of practice.
Special Conditions for Safe Use
The 'X' suffix to the certificate number relates to the following special condition(s) for safe use:
•
Parts of the enclosure may be non-conducting and may generate an ignition-capable
level of electrostatic charge under certain extreme conditions. The user should ensure
that the equipment is not installed in a location where it may be subjected to external
conditions (such as high-pressure steam), which might cause a build-up of electrostatic
charge on non-conducting surfaces.
• The end user must ensure that an ingress protection of at least IP65 is maintained at
each entry to the enclosure by use of a blanking element or cable entry device that meets
the requirements of the protection concepts type 'n' or increased safety 'e' or
flameproof 'd' .
•
The supply to the equipment shall be rated for a prospective short-circuit current of not
more than 10 kA and shall protected by a suitably-rated fuse.
Programming SITRANS LR560
Quick Start Wizard
• See
Quick Start Wizard via AMS Device Manager
• See
Activating SITRANS LR560
Power up the device. At initial startup, SITRANS LR560 will not begin measurements and all
blocks will be Out of Service until the instrument has been configured either locally or from a
remote location.
• Completing the Quick Start Wizard or writing any configuration parameter via the local
user interface causes the device to begin measuring. The Resource Block (RES) and
Level Transducer Block (LTB) will move to Automatic mode.
• AIFB 1 and AIFB 2 will remain Out of Service (as displayed on the LCD). These blocks can
only be configured and scheduled using a network configuration tool. For more details,
see System Integration in manual
(7ML19985MP01)
• A transition screen showing first the Siemens logo and then the current firmware revision
is displayed while the first measurement is being processed.
• The first time the device is configured you will be prompted to select a language (English,
German, French, Spanish or Chinese).
Page EN-12
SITRANS LR560 (FF) – QUICK START MANUAL
on page 14.
Foundation Fieldbus for Level Instruments
on page 19.
7ML19985XR81