b)
In the General field, click Master Reset then click Next to perform a reset to factory
defaults. Click Next to accept the default reset to Factory Defaults.
c)
Click FINISH, then scan the device (see step 3).
After a master reset is performed, the device will stop measuring, the Resource and Level
Transducer Blocks will go to Out of Service, and the LCD will display the Quick Start Wizard
until the device is configured.
3) Scan Device
Scan Device uploads parameters from the device to AMS Device Manager. This synchronizes
parameters between the device and AMS.
a)
From the menu bar, open the pull-down menu Actions – Scan Device.
b)
If you are adding a new device, configure the device via the Quick Start wizard.
Configuring a new device
Notes:
• The LR560 FF is shipped with RESOURCE and LTB blocks in Out of Service mode.
• After completing the Quick Start Wizard, via AMS or via local operation, you must
manually put the RESOURCE and LTB blocks into AUTO mode. (An exception is the first
time the Quick Start Wizard is completed via local operation
• Please consult the operating instructions or online help for details on using AMS Device
Manager.
1)
Changing Block Modes
Note: Resource Block overrides Level Transducer Block. Changing Resource Block mode will
also change Level Transducer Block mode.
To change any block mode follow the same procedure as for changing Resource Block mode.
To change Resource Block mode
1)
Navigate to Configure/Setup > Resource Block > Operation > Block Mode and click Block
Mode to open the dialog window.
2)
Select the desired Target mode and deselect the other option. Click Apply (the Apply
button is activated when a change is made).
1)
Then the RESOURCE and LTB blocks are automatically returned to AUTO mode.
Page EN-18
SITRANS LR560 (FF) – QUICK START MANUAL
1)
.)
Target Mode deselected
Target Mode selected
Apply
7ML19985XR81