Control units for 24Vdc motors with powers under 120W.
a) The electrical installation and operating logic must comply with statutory regulations.
b) Cables of different voltages must be physically separated or otherwise adequately screened with
secondary insulation of at least 1 mm.
c) Cables must be secured by additional clamps next to their terminals.
d) Control all wiring connections are correct before powering.
e) Check the Dip-Switch settings are correct.
f) Unused N.C. inputs must be jumpered.
Terminals
Function
(1-2)
Antenna
5
COM
6
Step by Step
7
STOP
8
PHOT
JP7
24Vdc Motor
JP10
Limit switch
14-15
Blinker
16-17
24 Vac
JP4
Secondary
J3
Radio Receiver
N.B.: To control the automation during installation, the Step by Step button on the control unit can be
used.
Control units CP.K
GENERAL RULES
INPUT/OUTPUT FUNCTIONS
Description
Optional antenna connection to built-in radio receiver board (1-
signal/2-screen).
If external antenna connected cut wire welded to "ANT".
Common for all control inputs.
Step by step button input (N.O. contact)
STOP button input (N.C. contact)
Input for safety devices, N.C. contact (e.g. photocells)
In close cycle: if the contact opens, the motor will stop and will in-
stantly reverse direction (opening).
In open cycle: disabled.
Jack for 24Vdc motor
Jack for limit switches:
A: SWC – Close limit switch
B: SWO – Open limit switch
C: COM – Common for limit switches
Blinker connection, 24Vac/15W max.
Accessory power supply 24Vac/1A max.
Secondary circuit of the transformer.
18 Grey: 0V output
19 Red: Slowdown speed.
Connect the Faston to the 15V output (minimum slowdown
speed) or 20V (maximum slowdown speed).
20 Brown: 24V output
21 White: Motor speed.
Connect the Faston to the 20V output (minimum motor speed)
or 30V (maximum motor speed).
See section "Motor speed adjustment "
Built-in radio receiver
7