Place the assembly pin over the temperature sensor.
6
Fix the brass screw fitting on the sensor using the assembly pin. For this purpose, the
7
installation direction of the grooved pin is to be observed.
Insert the temperature sensor with the screw fitting into the ball valve.
8
9
Tighten the brass screw fitting manually (without tool).
!
When installing in dip sleeves, the sensors must be pushed in down to the
bottom of the dip sleeve and then fixed.
Sealing
• After installation and inspection, the temperature sensor and the interface between
meter and pipeline must be sealed.
Information regarding connection of 4 wire temperature sensors
• Optionally, also 4 wire temperature sensors, such as head sensors, can optionally be
connected to the computer unit.
• The maximum cable length for the 4 wire temperature sensor Pt 500 is 25 m.
• The sensor located in the warmer section (T
sensor located in the colder section (T
connections for the cold meter vary).
Cold meter
This chapter only describes the properties and functions of the cold meter which differ
from those of the heat meter.
Operating conditions
• Flow sensor protection class
• Medium temperature
General installation instructions
• Always mount the computer unit separately from the volume measuring section
(e.g. using an optional mounting kit).
• Insulate the volume measuring section in an impermeable manner.
• This meter is not suitable for glycol/water mixtures (incorrect measurement).
• Lay the connection of the volume measuring section and temperature sensor to the
computer unit with a drip loop for condensation water.
• Always feed the cable into the computer unit from below.
Assembly of the volume measuring section
• Preferred installation location (condition as supplied):
- Cold meter outlet/high temperature
• Optional installation location (configuration change necessary)
- Cold meter inlet/low temperature
Installation of the temperature sensors
Information regarding connection of 2 wire temperature sensors (model PS)
• The sensor in the colder section (T
warmer section (T
Information regarding connection of 4 wire temperature sensors
• The sensor located in the colder section (T
• The sensor located in the warmer section (T
9
VL
) to clamps 7 and 8. Bridging is not required.
RL
) is installed on clamps 1, 5, 6 and 2. The
VL
) is installed on clamps 3, 7 , 8 and 4 (attention:
RL
9
IP 65
Θ: +3 °C...50 °C
4
) is connected to clamps 5 and 6, the sensor in the
) is installed on clamps 1, 5, 6 and 2.
VL
) is installed on clamps 3, 7 , 8 and 4.
RL
4