RANGE RATED CERTIFICATION
The maximum power, in heating mode, of Brava Slim HE 25/55
boilers can be adapted, during the installation, to
- 30/55 ErP
the thermal needs of the system by modifying the setting of
PAR 15 in the 0 .. 100 range.
The setting of PAR 15 = 100 is the factory setting that allows
the boiler to deliver its maximum power in heating mode. It
can be reduced by modifying the setting of PAR 15 as shown in
the table appearing below.
Example for Brava Slim HE 25/55 ErP boiler:
– default heating power range: 2,3 - 24,5 setting of PAR 15 = 100
– "reduced" heating power range: 2,3 - 20,1 setting PAR 15 = 80
DESCRIPTION
A - Factory power range
(heating)
B - Reduced power ranges for
maximum power reduction
(heating)
Boiler technical data plate
m
CAUTION
The grey fields must be filled in by the
installer.
66
25/55
Min
Max
kW
3,9
19,7
kW
3,9
18,1
kW
3,9
16,5
kW
3,9
15,0
kW
3,9
13,4
kW
3,9
11,8
kW
3,9
10,2
Once the new setting of PAR 15 has been made, the reduced
maximum power value (kW) for models with power above 35 kW
MUST MANDATORILY be applied beside the boiler's data plate.
For checks and adjustments after the modification, refer to
the new value for the maximum power.
The useful nominal power levels used are those relative to the
operating conditions (80-60°C) (Pn min - Pn max).
Brava Slim HE 25/55 - 30/55 ErP
30/55
Min
Max
4,7
23,6
4,7
21,7
4,7
19,8
4,7
17,9
4,7
16,0
4,7
14,2
4,7
12,3
Range Rated label
(only for models exceeding 35kW)
Factory power range
A
Reduced power range for maximum power
B
reduction
EN
Setting of PAR 15
100
90
80
70
60
50
40
A
B