HYDRAULIC CONNECTIONS
The pipes that connect the tank tothe burner should be in perfect tight condition; we recommend the use of copper or steel pipes of an adeguate diameter.
Fuel gate valves should be fitted at the end of the rigid pipelines.Fit the filter to the suction pipeline after the gate valve. Connect the flexible fitting to this,
which in turn should be connected to the suction of the burner pump. Connect the flexible fitting to the return pipe after the gate valve, and then connect
it ot the pump return. Filter, flexible pipes and relative connecion nipples are standard burner accessories. The pump is provided with special connection
points for the insertion of control instruments (manometer and vacuumeter).To ensure reliable and silent operating conditions, the vacuum in suction
should not exceed 35 cm Hg equal to 0,46 bar.Maximun suction and return pressure 1,5 bar.
E
N
G
L
I
S
H
1 Oil tank
2 Feed line
3 Filter
4 Burner
5 Degasifier
N.B. For any missing devices in the
pipping, conform to existing regulations.
H
= Measurement between minimum oil level and pump axis
L
= Max. legth of suction line, including vertical lifts. For each bend of valve deduct 0,25 m.
Ø i = Internal diameter of pipe
6 / 14
0006080735_201104
GRAVITY FEED FROM THE BOTTOM OF OIL TANK
6 Suction line
7 Return line
8 Fire valve
9 Non return valve
GRAVITY FEED OVER THE TOP OF OIL TANK
1 Oil tank
7
3 Filter
8
4 Burner
9
6 Suction line
10 Foot valve
SUCTION FEED
1 Oil tank
6
3 Filter
7
4 Burner
10 Foot valve
H
meters
0,5
1
1,5
2
2,5
3
3,5
H
Total meters
meters
Ø i. 10 mm.
1
30
2
35
3
40
4
45
Return line
Fire valve
Non return valve
H
Total meters
meters
Ø i. 10 mm.
1
30
2
35
3
40
4
45
Quote P = 3,5 m (max)
Suction line
Return line
Total meters
Ø i. 10 mm.
Ø i. 12 mm.
26
54
24
47
18
38
14
30
10
23
6
15
-
7

Publicidad