Making Presettings In Windp - Aventics RMV04-8DI_M8 Instrucciones De Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 281
AVENTICS | PROFIBUS DP | R499050016–BDL–001–AE
The GSD file can be downloaded from the Internet at
www.aventics.com.
During commissioning of a bus coupler controlling 32 valve
solenoids (R412008079), a GSD file version  1.3 must be used.

7.2.2 Making presettings in WinDP

The WinDP utility program runs on top of WinSPS. Only existing
PLC projects can be worked on with the WinDP software.
1. Start the WinDP program.
2. Access "WinDP Voreinstellungen" dialog window (WinDP
presettings).
Fig. 11: WinDP presettings dialog window
3. In the "Projektpfad " (project path), enter the directory in
which the PLC project is stored. The project name found there
is then put into the "Voreinstellungen" (presettings) field.
4. In the "Gerätestammdaten" (device master data) field, enter
the directory in which the master data (GSD) was copied
(see "Loading device master data" on page 112).
5. Verify the information with "OK".
Commissioning and Operation
113

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rmv04-8di_m12

Tabla de contenido