Fig. 13: WinDP editor dialog window, window designations
1 Work area
2 Bus slave window
2a Bus coupler designation
AVENTICS | PROFIBUS DP | R499050016–BDL–001–AE
2b Valve system and modules
3 I/O window
2. In the bus slave window, select the bus coupler of the valve
system in order to configure the system as a slave in
PROFIBUS DP.
The valve system's slaves are found in the
bus slave window under "Norm-Slaves", I/O.
The valve system bus coupler has the designation "RMV04-DP".
3. Click on the bus slave "RMV04-DP".
4. Hold down the left mouse button and drag the bus slave to
the left and drop it onto the bus master in the work area. As
soon as a square with a "+" appears under the cursor, you
can drop the bus slave by letting go of the left mouse button.
WinDP draws the bus line from the master to the new bus slave
"RMV04-DP" and assigns it to the next available bus address.
Commissioning and Operation
2
2a
2b
3