AVENTICS | PROFIBUS DP | R499050016–BDL–001–AE
W
You have made presettings and configured the system (see
"Making presettings" on page 101 and "Configuring the bus
coupler with WinDP" on page 111).
W
You have configured the bus master so that it controls the
valves and the input module correctly.
W
You have carried out the diagnostic test on the input/output
modules (see "Testing and diagnosis on the bus coupler" on
page 124).
Commissioning and operation may only be carried out by
qualified electrical or pneumatics personnel or an instructed
person under the direction and supervision of qualified
personnel (see "Personnel qualifications" on page 79).
Uncontrolled actuator movements when the pneumatics are
switched on
Danger of injury if the system is in an undefined state and the
manual overrides are set to position "1".
O
Put the system in a defined state before switching it on.
O
Set all manual overrides to position "0".
O
Make sure that no personnel are within the hazardous
zone when the pressure is switched on.
O
Also observe the applicable instructions and safety
information in the VS operating instructions.
1. Switch on the operating voltage.
2. Check the LED displays on all modules.
3. Switch on the compressed air supply.
Commissioning and Operation
CAUTION
127