Connecting The Bus Coupler As An Intermediate Station - Aventics RMV04-8DI_M8 Instrucciones De Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 281
BU S I N
X71
2
1
3
4
5
BU S O UT
X72
1
2
5
4
3
1
2
AVENTICS | PROFIBUS DP | R499050016–BDL–001–AE
Tab. 4:
Assignment X71 (BUS IN) and X72 (BUS OUT), M12, B-coded
Pin Signal
Meaning
1
VP
Supply voltage + (P5V)
1)
2
RxD/TxD-N
Receive/send data N, data line A (green)
3
DGND
Reference potential to VP, 0V
1)
4
RxD/TxD-P
Receive/send data P, data line B (red)
5
Shield
Shield or protective grounding
Housing
Shield or protective grounding
1)
The assignment of the green bus cable wire to data line A (RxD/TxD-N)
and of the red wire to data line B (RxD/TxD-P) is not standardized.
AVENTICS recommends the assignment shown in the table.
When using a cable with a filler cord, this can be additionally
connected to pin 5 on the bus plug (X71, X72).
The connection technology and plug assignment comply
with the specifications in the "Interconnection Technology"
technical directives (PNO order no. 2142).
6.3.2 Connecting the bus coupler as an intermediate
station
1. Set up the correct pin assignments (see Table 4 on page 93)
on the plug connections if you do not use pre-assembled
wiring.
2. Connect the incoming bus connection to X71 (1).
3. Connect the outgoing bus cable with the next module using
the X72 output (2).
4. Remove the PG fitting B.
5. Set switches S7 and S8 to "OFF" (bus terminator = OFF,
see also "Setting the bus terminator" on page 110).
6. Screw the PG fitting B back in. Pay attention that the sealing
ring is positioned correctly.
7. Connect the shield on both sides of the bus cable directly to
the plug housing (EMC housing) if non-pre-assembled
cables and plugs with metal housing are used. This protects
data lines from terminal interference.
93
Assembly

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rmv04-8di_m12

Tabla de contenido