Descargar Imprimir esta página

nVent RAYCHEM SC-JBS-L-A Instrucciones De Instalación página 5

Publicidad

Idiomas disponibles

Idiomas disponibles

14
• Crimp heating cable conductors together and use only the specified crimp
tool, die and splices to ensure a proper electrical connection (see table).
Improperly crimped connection can result in overheating.
• Smooth down any sharp wires after crimping to prevent wires from poking
through tape strips in Step 17.
Heating
cable con-
(1)
Heating cable
ductor size
2 and 3SC60-CT 12 AWG
2 and 3SC70-CT 10 AWG
2 and 3SC80-CT 8 AWG
(1)
The above table is also applicable for 2 and 3SC/H60, 70, 80 (-CT) and 2 and 3SC/
F60, 70, 80 (-CR) heating cables. For additional splices, call nVent at (800) 545-6258.
15
• Crimp braid wires together using the TBM5S crimp tool, specified die and splice.
Thomas & Betts (T&B) Splice
Splice
(1)
Heating cable
catalog no.
2SC60, 70 and 80-CT
54610
3SC60 and 70-CT
54615
3SC80-CT
54620
(1)
The above table is also applicable for 2 and 3SC/H60, 70, 80 (-CT) and 2 and 3SC/
F60, 70, 80 (-CR) heating cables. For additional splices, call nVent at (800) 545-6258.
16
WARNING: Fire and Health Hazard. Soldering tools or minitorches can cause fire or explosion
in hazardous areas. Be sure there are no flammable materials or vapors in the area before
using these tools. Follow all site safety guidelines when working in hazardous areas.
Refer to solder material safety data sheet packaged with kit.
Do not overheat or char the conductor insulation. Inhalation of fumes can cause polymer
fume fever, flu-like symptoms, irritation, and difficulty breathing.
Do not direct torch flame toward conductor insulation, cold lead insulation, or enclosure.
Damage to insulation or enclosure can lead to shorting or moisture ingress.
• Use only solder provided with the kit. Only Kester 48 core LF has been qualified for use with
SC cables.
• Heat each splice using a soldering tool, or propane or MAPP gas torch. Note: MAPP gas may
be required if the connections are being soldered at temperatures below –4°F (–20°C). Heat
the center of the splice until it is hot enough to melt the solder placed at both ends. Allow
the splices to cool for several minutes before proceeding to the next step of wrapping the
connection with tape.
Thomas & Betts (T&B) Splice
Splice
Crimp tool
catalog no. Splice color
catalog no.
C10-PS-D
Silver
WT2000
54615
Grey
TBM5S
54620
Brown
TBM5S
Crimp tool
Splice color
catalog no.
Blue
TBM5S
Grey
TBM5S
Brown
TBM5S
Crimp tool
die
Non-Insul
Grey
Brown
Trim off
sharp edges
after crimping
Crimp tool
die letter
Blue
Grey
Brown
Trim off
sharp edges
after crimping
3SC heating
cable shown.
Heating
Heating
cable "A"
cable "B"
3SC heating
cable shown.
3SC heating
cable shown.
nVent.com | 5