Technical Data; Model Identification; Commissioning The Device; Operations Prior To Installation - Madas XVF-1 Manual Del Usuario

Electroválvula automática normalmente cerrada para gas
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2.0 - TECHNICAL DATA

• Use
• Ambient temperature (TS)
• Supply voltages (see table 2)
• Supply voltage tolerance
• Electric wiring
• No. cycles/hour**
• Absorbed power
• Maximum operating pressure
• Total obturator opening time
(ta= 25°C Vn=230 V)
• Opening time range (on slow versions)
• Protection rating
• Coil protection mode
• Class
• Mechanical strength
• Flanged connections that can be coupled to PN 16 flanges : (DN 200) ISO 7005 / EN 1092-1
• ANSI 150 flanged connections
• In compliance with
* Only single-phase, the device does not work if powered with three-phase voltage.
** For cycles/hours with ON/OFF times different from those specified, contact our technical office

2.1 - MODEL IDENTIFICATION

XVF- : Fast opening + flow adjustment
XVR- : Adjustable slow opening + flow adjustment
1 : P. max 1 bar
3 : P. max 3 bar
6 : P. max 6 bar
E.g.:
XVR-3 = Automatic NC solenoid valve with adjustable slow opening + flow adjustment - max P. 3 bar

3.0 - COMMISSIONING THE DEVICE

3.1 - OPERATIONS PRIOR TO INSTALLATION

All installation operations must be carried out in the absence of an explosive atmosphere.
• It is necessary to close the gas upstream of the valve prior to installation;
• Make sure that the line pressure DOES NOT EXCEED the maximum pressure declared on the product label;
• Any protective caps (if any) must be removed prior to installation;
• Valve pipes and insides must be clear of any foreign bodies;
• make sure the inlet and outlet counter-flanges are perfectly coaxial and parallel in order to prevent unnecessary mechanical
stress to the body. Also calculate the space to insert the seal gasket;
• With regard to tightening operations, equip yourself with one or two calibrated torque wrenches or other controlled locking
tools;
• The safety regulations on handling loads in force in the country of installation must be complied with. If the device to
be installed exceeds the weight allowed, suitable mechanical equipment and adequate slings must be used. Necessary
precautions must be taken during the handling phases in order not to damage/ruin the external surface of the device.
• In accordance with EN 161, a suitable filter must be installed upstream of a gas closing safety device;
• With outdoor installation, it is advisable to provide a protective roof to prevent rain from damaging the electrical parts of
the device.
• Prior to carrying out any electrical wiring operations, make sure that the mains voltage matches the supply voltage indicated
on the product label;
XVF-1-3-6 - XVR-1-3-6
: non-aggressive gases of the three families (dry gases)
: -20 ÷ +60°C
: 24 Vdc - 24 V/50 Hz - 110 V/50 Hz - 230 V/50 Hz*
: -15% ... +10%
: electric cable l=3 metres with wire terminals
:
20 (ON time 30s - OFF time 150s)
~
: see table 2
: 1 bar, 3 bar or 6 bar (see product label)
:
30 s
± 20%
: up to 45 s ± 20% (ta= 25 °C Vn=230 V)
: IP65
: II 3G Ex ec nC mc IIC T4 Gc X - II 3D Ex tc IIIC T135°C Dc X
: A
: Group 2
: on request
: PED Directive 2014/68/EU - EMC Directive 2014/30/EU
EN 60079-0-7-14-15-31 - ATEX Directive 2014/34/EU
LVD Directive 2014/35/EU - RoHS II Directive 2011/65/EU
12
Madas Technical Manual - 1|1.5eX - REV. 0 of 1
Aug 2019