2.0 - TECHNICAL DATA

• Use
• Ambient temperature (TS)
• Supply voltages (see table 2)
• Power supply tolerance
• Electric wiring
• Absorbed power
• Maximum operating pressure
• Closing time
• Protection rating
• Coil protection mode
• Class
• Mechanical resistance
• Rp Threaded connections
• NPT Threaded connections
• Filter element
• In compliance with
* Only single-phase, the device does not work if powered with three-phase voltage.

2.1 - MODEL IDENTIFICATION

M14/RMJ N.C.
: Die-cast aluminium body (Rp DN 15 - Rp DN 20 - Rp DN 25) - max P. 0.5 bar
M14/RMCJ N.C.
: Die-cast aluminium body (Rp DN 25 compact)
M16/RMOJ N.C. : Brass body (Rp DN 15 - Rp DN 20 - Rp DN 25)

3.0 - COMMISSIONING THE DEVICE

3.1 - OPERATIONS PRIOR TO INSTALLATION

All installation operations must be carried out in the absence of an explosive atmosphere.
• It is necessary to close the gas upstream of the valve prior to installation;
• Make sure that the line pressure DOES NOT EXCEED the maximum pressure declared on the product label;
• Any protective caps (if any) must be removed prior to installation;
• Valve pipes and insides must be clear of any foreign bodies;
• Make sure that the pipe thread is not too long, to prevent damaging the body of the device when screwing it on;
• In accordance with EN 161, a suitable filter must be installed upstream of a gas closing safety device;
• With outdoor installation, it is advisable to provide a protective roof to prevent rain from damaging the electrical parts of
the device;
• Prior to carrying out any electrical wiring operations, make sure that the mains voltage matches the supply voltage indicated
on the product label;
• Cut off power prior to proceeding with wiring;
• According to the plant geometry, check the risk of an explosive mixture arising inside the piping;
• If the solenoid valve is installed near other devices or as part of an assembly, compatibility between the solenoid
valve and this other device must be evaluated beforehand;
• Avoid installing the solenoid valve near surfaces that could be damaged by the coil temperature. ATTENTION:
the surface temperature could cause contact burns. If it is installed in a domestic environment, it must not be
accessible to unqualified personnel;
• The solenoid valve is suitable for installation in places at low risk of mechanical impact. Provide a protection against
impacts or accidental contacts if the solenoid valve is accessible to unqualified personnel.
M14/RMJ N.C. - M14/RMCJ N.C. - M16/RMOJ N.C.
: non-aggressive gases of the three families (dry gases)
: -20 ÷ +60°C
: 12 Vdc, 12 V/50 Hz, 24 Vdc, 24 V/50 Hz, 110 V/50-60 Hz, 230 V/50-60 Hz*
: -15% ... +10%
: electric cable l=3 metres with wire terminals
: see table 2
: 500 mbar (M14/RMJ N.C. - M14/RMCJ N.C.)
500 mbar - 6 bar (M16/RMOJ N.C. - see product label)
: <1 s
: IP65
: II 3G Ex mc ec nC IIA T4 Gc X - II 3D Ex mc tc IIIC T135°C Dc X
: A
: Group 2
: (DN 15 - DN 20 - DN 25) according to EN 10226
: request feasibility
: 1 mm wire mesh (only for M14/RMJ N.C. - M14/RMCJ N.C.)
: Regulation (EU) 2016/426 (Appliances burning gaseous fuels)
EN 60079-0-7-14-15-18-31 - ATEX Directive 2014/34/EU
PED Directive 2014/68/EU (versions with P.max = 6 bar)
EMC Directive 2014/30/EU - LVD Directive 2014/35/EU - RoHS Directive II 2011/65/EU
10
- max P. 0.5 bar
- max P. 0.5 - 6 bar - ATEX 3G - 3D
Madas Technical Manual - 2|2.1aJ - REV. 0 of 1
- ATEX 3G - 3D
- ATEX 3G - 3D
Aug 2019