1.6 TECHNICAL DATA

Circuit breaker
Standard
Maximum rated current (40 °C) - In max. (A)
Current setting
Rated operational voltage - Ue (V)
Rated insulation voltage - Ui (V)
Impulse voltage - Uimp (kV)
Frequency (Hz)
Number of poles
Versions
Protection units
Rated ultimate short-circuit
breaking capacity - Icu (kA)
Rated service short-circuit
breaking capacity - Ics (kA)
Rated short-time withstand current
- Icw (kA)
Rated making capacity
- Icm (kA peak)
Utilization categories
Operating time (ms)
Mechanical lifespan
(number of operations)
Electrical lifespan
(number of operations)
Altitude (m)
Ambient temperature
Weight (kg)
4)
Connection terminals -
withdrawable/fixed
External dimensions
H x W x D (mm)
Notes: 1) According to the maintenance routines indicated in the manual.
2) For installation above 2,000 m from sea level, please consider the voltage and current derating factors, as shown in the chart below.
3) For ambient temperature above 40 °C, check maximum rated current values in the chart below.
4) It may vary according to the configuration of optional accessories.
ABW08 ABW16 ABW20 ABW25 ABW32 ABW40 ABW50
800
220 / 380 / 415 V
440 / 480 / 500 V
600 / 690 V
220 / 380 / 415 V
440 / 480 / 500 V
600 / 690 V
1s
2s
3s
220 / 380 / 415 V
440 / 480 / 500 V
600 / 690 V
Opening (max.)
Closing (max.)
Without maintenance
20,000
With maintenance
30,000
1)
Without maintenance
5,000
With maintenance
10,000
1)
Operation
Storage
Withdrawable
Fixed
Horizontal
Standard
Vertical
Optional
Withdrawable
430 x 334 x 375
Fixed
300 x 300 x 295
Table 1.5: Technical data
IEC 60947-2
1,600
2,000
2,500
(0.4 ~1.0) x In max
690
1,000
12
50 / 60
Fixed - withdrawable
LSIG Electronics
65
85
65
85
50
85
65
85
65
85
50
85
50
85
42
75
36
65
143
187
143
187
105
187
40
80
15,000
20,000
5,000
10,000
≤2,000
-5...40 °C
-20...60 °C
61
85
32
42
Standard
Optional
430 x 412 x 375
300 x 378 x 295
www.weg.net
ABW63
3,200
4,000
5,000
6,300
3
100
100
85
100
100
85
85
75
65
220
220
187
B
10,000
10,000
15,000
15,000
2,000
2,000
5,000
5,000
2)
3)
143
74
Standard
Standard
Optional
Optional
430 x 629 x 375
430 x 785 x 375
300 x 597 x 295
300 x 751 x 295
ABW - Air Circuit Breaker | 15
120
120
100
120
120
100
100
90
85
264
264
220
184
101

Publicidad