5 FEATURES AND INSTALATION INSTRUCTIONS

5.1 EARTH LEAKAGE ADJUST:

Leakage current can be adjusted between 0.5 A until 30 A, according to table below, ground fault protection
must to be disable:
Current setting
I n
Time delay
t
Accuracy

5.2 DIMENSIONS:

5.2.1 Toroidal CT WEG (30/5 A ratio)

2 models available:
Model
A
ZCT-120
120
ZCR-200
200

5.3 EXTERNAL CT INSTALATION

Toroidal CT must be connected on buses/conductors of breaker supply. Two secundary signal conductores of
external CT must be connected on E1 and E2 protection unit terminals, a conductor in each terminal. Toroid has
5 A secundary signal, consider conductor to link CT signal for this current intensity.
42 | ABW - Air Circuit Breaker
Earth leakage (optional)
0.5
1
Alarm time
140
230
Trip time
140
230
Table 5.1:
Figure 5.1: Toroidal CT WEG (30/5 A ratio).
B
C
45
225
53
310
Figure 5.2: External CT instalation.
2
3
5
350
800
950
350
800
D
E
180
210
260
286
ZCT or
CT External
10
20
30
F
G
20
55
20
70
Off
H
35
35