3.3.2 Extraction
1. Maintaining the OFF button
pressed, insert the extraction
rod in the hole located in
the lower part of the circuit
breaker.
4. At this moment the lock
comes out (LOCK).
6. At this moment the lock
comes out again (LOCK).
2. Press the position lock.
3. Turn the extraction rod a
few times in a counterclockwise
direction, until the circuit breaker
reaches the TEST position.
5. Press the position lock.
Turn the extraction rod a
few times in a clockwise
direction, until the circuit
breaker reaches the
CONNECTED position.
7. When the circuit
breaker is in the
DISCONNECTED
position, the rails can be
unlocked, pulling it out and
removing it from the
extraction car.
Figure 3.6: Extraction