2.3 Safety symbols on the pump
Check the position of the clamp before you tighten it.
Incorrect position of the clamp will cause leakage
from the pump and damage the hydraulic parts in the
pump head.
Fit and tighten the screw that holds the clamp to 6 ±
0.7 ft-lbs (8 ± 1 Nm).
Do not apply more torque than specified even though
water is dripping from the clamp. The condensed
water is most likely coming from the drain hole under
the clamp.
3. Receiving the product
3.1 Inspecting the product
Check that the product received is in accordance with the order.
Check that the voltage and frequency of the product match
voltage and frequency of the installation site. See section
7.4.1 Nameplate.
Pumps tested with water containing anticorrosive
additives are taped on the inlet and outlet ports to
prevent residual test water from leaking into the
packaging. Remove the tape before installing the
pump.
3.2 Scope of delivery
3.2.1 Terminal-connected single-head pump
The box contains the following items:
•
MAGNA3 pump
•
insulating shells
•
gaskets
•
quick guide
•
safety instructions
•
box with terminal and cable glands
•
conduit adapter, 20 mm to 1/2" NPT.
6
3.2.2 Terminal-connected twin-head pump
The box contains the following items:
•
MAGNA3 pump
•
gaskets
•
quick guide
•
safety instructions
•
two boxes with terminals and cable glands
•
conduit adapter, 20 mm to 1/2" NPT.
3.2.3 Wire-to-wire-connected single-head pump
The box contains the following items:
•
MAGNA3 pump
•
insulating shells
•
gaskets
•
quick guide
•
safety instructions.