Differential Temperature; Constant Curve - Grundfos MAGNA3 D Instrucciones De Instalación Y Operación

Ocultar thumbs Ver también para MAGNA3 D:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

8.3.7 Differential temperature

Select this control mode if the pump performance is to be
controlled according to a differential temperature in the system
where the pump is installed.
Characteristics and key benefits
Ensures a constant differential temperature drop across
heating and cooling systems.
Ensures a constant differential temperature between the pump
and the external sensor, see figures 31 and 32.
Requires two temperature sensors, the internal temperature
sensor together with an external sensor.
Technical specifications
H
Fig. 31 Differential temperature
Temperature sensor
To measure the temperature difference of the flow and return
pipe, you must use both the internal sensor and an external
sensor.
If the pump is installed in the flow pipe, the external sensor must
be installed in the return pipe and vice versa. Always install the
sensor as close as possible to the consumer (radiator, heat
exchanger, etc.). See fig. 32.
Fig. 32 Differential temperature
26
Δt
Q
t

8.3.8 Constant curve

A constant curve is suitable for systems where there is a demand
for both constant flow and constant head, i.e.:
heating surfaces
cooling surfaces
heating systems with 3-way valves
air-conditioning systems with 3-way valves
chiller pumps.
Characteristics and key benefits
If an external controller is installed, the pump is able to change
from one constant curve to another, depending on the value of
the external signal.
Depending on your preferences, the pump can be controlled
according to either a maximum or minimum curve.
Technical specifications
H
Fig. 33 Constant-curve mode
The pump can be set to operate according to a constant curve,
like an uncontrolled pump. See fig. 33.
Q

Publicidad

Tabla de contenido
loading

Tabla de contenido