Group error
Error, designation cause;
message
effect/action
menu line no.
8-4- 11
Treatment (optional)
First message (warning), 70% of the treatment volume entered
in the menu has been reached.
Prepare replacement module! Reset error message.
Second message (warning), 90% of the treatment volume
entered in the menu has been reached. This message replaces
the first message , if no. 55 has not been reset. The value on the
display is inverted and flashes. Prepare replacement module!
(if necessary, replace module, observe error message no.: 31)
Third message (warning), 100% of the treatment volume
entered in the menu has been reached. This message replaces
the first message , if no. 61 has not been reset. The value on the
display is inverted; top-up is interrupted.
May be followed by error no. 19. To maintain the pressure
(pressure increase), replace the module, reset the value, and
then, if necessary, modify the entry for possible treatment
volume, see page 32.
Maintain. 1
8-4- 12
Carry out maintainance 1 (equipment service)
8-4- 13
Maintain. 2
Carry out maintainance 2 (inspect vessel internally)
8-4- 14
Maintain. 3
Carry out maintainance 3 (inspect vessel strength)
(Maintain. 4)
8-4- 15
Carry out maintainance 4 (routine electronic installation
inspection)
Date/ time invalid
Backup power for date, time is too small, not available or incor-
8-4- 16
rect line entry of these data / redo or complete entry or when
after complete entry error recurs » service Error OFF; error is
self-resetting after resolving.
SPCx-hw: Phase monitor (option)
Phase is missing or phase sequence is incorrect, motors and
valves are turned off, no pressure increase or reduction; note:
8-4- 17
the equipment supplied is installed for operation with clock-
wise rotating field (U/L1; V/L2; W/L3) / locate phases, check
power supply fuse for this equipment, switch wiring for correct
sequence; Error OFF, error is self-resetting after resolving.
7.9. Restarting
After long periods of downtime:
• I f this downtime was planned or scheduled, turn
OFF the control unit and close off the lockshield
valves to the system and the isolating valve to the
top-up line. After that decompress and then drain
the water area. We recommend you carry out
maintenance before restarting (see Maintenance
section).
• Use the commissioning records for restarting and
check especially for system changes that can lead
to other operating conditions of the expansion
automat (e.g. system pressure).
If the power supply has failed:
• T he target parameters and default settings
for pressure, aeration and top-up will remain
Installation and operating instructions Wilo-Sinum
Default
Value
setting
OFF
70%
90%
100%
OFF
365d
OFF
1825d
OFF
3650d
OFF
584d
OFF
OFF
unchanged, meaning automatic operation will
resume automatically when power is restored
(control unit ON). Extraordinary system opera-
ting conditions (e.g. cooling to below the default
setting) may fall outside the permitted settings of
the expansion vessel.
Caution: please ensure that when the system
cools down or warms up, the minimum or ma-
ximum system pressure does not exceed or fall
below the permitted operating pressure. Under-
and over-pressure safety for operation of heating
or cooling systems are not within the standard
scope of supply of the Wilo-Sinum.
Check the automat's operation once power
supply has been restored and, if necessary, set
the actual date and time values (overview menu
options).
English
Error message
number
55
61
31
56
57
58
59
53
30
69