BTL7-A/C/E/G _ _ _ -M _ _ _ _ -A(8)-SA211/SA311-S32/S115/S135/KA_ _/FA_ _
Magnetostrictive Linear Position Sensor – Rod Style
6
Calibration procedure (continued)
6.3.2
Adjusting
The detailed procedure for adjusting is
described on page 18 ff.
A new start and/or end value is adjusted. This is
recommended when the magnet cannot be brought to the
zero point or end point.
Steps:
► Move magnet to the new start position.
► Set the new start value by pressing the buttons.
New start value
Zero point
Figure 6-4:
Adjusting new start position (offset shift)
► Move magnet to the new end position.
► Set the new end value by pressing the buttons.
Before
After
Figure 6-5:
Adjusting new end position (changing the output
gradient)
www.balluff.com
6.3.3
Setting start and end values while the system is running.
6.3.4
Restoring the BTL to its factory settings.
6.4
Before
After
Teach-in
1
Zero
point
New end value
End point
Figure 6-6:

Online setting

The detailed procedure for online setting is
described on page 20.
Reset
The detailed procedure for the reset is
described on page 21.

Selecting the calibration procedure

Buttons inactive
1
/
1
2
+
1
2
Buttons active
1
1
+
2
2
1
Reset
Adjusting
2
1
2
End
Zero
End
point
point
point
Buttons inactive
1
1
2
1
+
2
+
1
1
1
2
Buttons active
Online
Online
setting
setting
End point
Zero point
Selecting the calibration procedure
english
15