level, the pump will return to normal running conditions. It will not be
possible to start the pump manually as long as the temperature is
too high.
Related information
6.14 Setting the maximum number of restarts with Grundfos GO
Remote
8.10 Code 69 (Winding temperature too high)
6.17.2 Overload protection
The pump is protected by a motor-protection relay. The nominal
current draw must be set manually on the motor-protection relay.
See the specific documentation for the relay on how to set the
trigger level. If the current exceeds the trigger level, the relay will
switch off the pump and the controller will give an alarm. The alarm
has to be manually reset directly on the motor protection relay.
Related information
6.14 Setting the maximum number of restarts with Grundfos GO
Remote
8.8 Code 48 (Motor is overloaded)
6.17.3 Moisture protection
When a moisture sensor is installed in series with the temperature
sensor, the control unit needs to know how to determine whether
there is a high temperature or moisture in the pump. If the
temperature is too high, normally the temperature sensor will go
back to its normal stage when the temperature has dropped to its
trigger level. If there is moisture in the pump, then the moisture
sensor will keep the series connection open until the pump is
opened and serviced.
To determine which sensor has been active, a cool down
time must be entered. This is the time that will normally pass until
the temperature has dropped enough for the temperature sensor to
return to its normal stage. If the cool down time is exceeded, the
control unit will assume that there is moisture in the pump, and it
will send a moisture alarm.

6.18 Alarm reset

6.18.1 Resetting alarms and warnings manually with Grundfos
GO Remote
1.
Go to Alarms and warnings.
2.
Press Reset alarm.
All current alarms and warnings have been reset. However, if
the fault causing the alarm or warning has not been removed,
the alarm or warning will appear again.
3.
If you want to delete all alarms and warnings from the history
log, press Show log > Reset alarm and warning logs.
6.18.2 Setting the automatic alarm reset with Grundfos GO
Remote
1.
Go to Settings > Automatic alarm reset.
2.
Select one of the following:
No automatic reset
All except pump critical
All alarms
6.18.3 Resetting alarms and warnings on the operating panel
You can manually reset alarms and warnings on the operating
panel. However, if the fault causing the alarm or warning has not
been removed, the alarm or warning will appear again.
1.
Press Reset on the operating panel to reset the alarm or
warning.
18
The control unit does not
reset any alarm or warning.
You must do it manually.
The control unit resets alarms
and warnings unless the
related fault can damage the
pump.
The control unit resets alarms
and warnings, regardless of
the fault.

6.19 Setting the buzzer with Grundfos GO Remote

The internal buzzer is used to give an acoustic sound if there is a
warning or an alarm.
1.
Go to Settings > Buzzer settings.
2.
Select when the buzzer is to be activated:
• All alarms
• All alarms and warnings.

6.20 Setting units for Grundfos GO Remote

Changing units as described here will only change the units shown
in Grundfos GO Remote. It will not affect the units shown on the
operating panel of products connected to Grundfos GO Remote.
1.
Press the Menu button in the upper left corner of Grundfos GO
Remote.
2.
Go to General > Settings > Products > Units.
3.
Select US or Grundfos default units.
6.21 Setting units for the operating panel with Grundfos
GO Remote
Changing units as described below changes the units shown in the
operating panel of the product connected to Grundfos GO Remote.
It does not affect the units shown in Grundfos GO Remote.
1.
Go to Settings > Display units.
2.
Select the units to be used on the operating panel.
• SI Units
• US Units.

6.22 GENIbus

GENIbus, the Grundfos Electronics Network Intercommunications
bus, is a fieldbus developed by Grundfos to meet the need for data
transfer in all typical Grundfos motor or pump applications.
Grundfos devices with GENIbus can be wired together in networks
and integrated in automation systems. Each device on the network
must have a unique GENIbus address. GENIbus is based on the
RS485 hardware standard and typically operates at a baud rate of
9600 bits/s.