Burner Adjustments; Main Hydraulic Circuits - Sime ESTELLE HE B4 INOX ErP Manual De Uso, Instalación Y Mantenimiento

Ocultar thumbs Ver también para ESTELLE HE B4 INOX ErP:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5.7

Burner adjustments

The suggested adjustments for the operation of the combinable burner installed at sea level are shown in the table.
Description
ESTELLE HE B4 INOX ErP
Values obtained during operation
(**)
When the burner is installed at altitudes up to maximum 1300 m.a.s.l., due to the lower air density, the factory adjustments for the
burner must be modified as follows:
– Keep the nozzle mounted in the factory
– Do not vary the position of the combustion head
– Gradually reduce the pump pressure to reduce the fuel flow rate
– Adjust the air shutter by taking the following readings:
- CO
(%)
2
- CO (ppm) (as per the regulations in force)
- Bacharach index (≤ 0,5)
- Flue gas temperature.
5.8

Main hydraulic circuits

9
R
13
15
14
80
Model
Code
SIME FUEL 35 EV
8118503
(Vers. HE)
11
8
7
U
RC
E
M
1
10
Nozzle
Pulverisation
angle
Type
GPH
DANFOSS
0,65
60°H
12
2
12
3
6
4
Pump
NOx
pressure
class
(bar)
12
3
KEY:
Boiler body
1
Water pressure switch
2
Automatic bleed valve
3
Stub pipe G1" (to be replaced
4
with a system pump if neces-
sary)
Calorifier circulator pump
5
Check valve (VR)
6
Fitting for calorifier safety valve (VS)
7
6
Magnesium anode
8
Hot water tank drain valve (SB)
9
System discharge valve (SI)
10
Storage tank
11
Manual relief valve
12
5
Heat recovery device
13
Siphon
14
Condensate outlet (SC)
15
M
System delivery
System return
R
Domestic hot water output
U
Domestic hot water inlet
E
RC
Recirculation
EN
Absorbed
electrical
power (*)
(W)
168
Fig. 19

Publicidad

Tabla de contenido
loading

Tabla de contenido