– The flue must be sized correctly for condensing
boilers. Inadequate or incorrectly sized flues can al-
ter the combustion parameters and generate noise.
– It is recommended that a condensate neutraliser be
installed before discharging it into the waste water
drain.
– Ensure that the duct and condensate outlet pipes
have an angle of at least 3% towards the neutraliser
or the drain.
– Mount an adequate filter to prevent dust or dirt from
being drawn in.
6.10

Condensate outlet/collection

m
CAUTION
– The condensate outlet duct must be airtight, suita-
bly sized to that of the siphon and must not be re-
stricted at any point.
– The condensate outlet must be constructed in full
compliance of the National or Local regulations in
force.
– It is recommended that a condensate neutralising
unit be provided and the pipework should have a
downward angle of at least 3%.
– Before commissioning the appliance, fill the siphon
with water.
d
IT IS FORBIDDEN
The flue condensate discharge pipe MUST NOT return
back into the appliance, but must be kept separate
from the boiler pipe, in accordance with the indica-
tions of the appliance's manufacturer and the laws in
force in the country of installation.
90
6.11
The Sime ESTELLE HE B4 INOX ErP boiler requires the connec-
tions shown below, which must be carried out by the installer or
by professionally qualified personnel.
To connect the electrics:
– remove the front panel (1) to access the control panel
– loosen the screws (2) that fasten the control unit cover (3).
– turn the cover (3) downwards to access the internal terminal
block (MIQ).
The cables must enter from the rear of the boiler and must then
be locked, once the job has been completed, with the tear-proof
cable clip already fitted. Once the connections have been made,
reassemble the previously dismantled elements.
2
x6
1
NC
Fig. 34
Connections to be made by the installer
The electrical connections to be made include:
– power supply 230V - 50Hz with magnetothermic switch
– connection of the room thermostat (TA) or timer-controlled
thermostat, after having removed the jumper between termi-
nals 20 and 21
– if a time programmer is used, remove the bridge between
terminals 30 and 31 and connect the programmer timer-con-
trolled thermostat (CTP) to terminals 28, 29, 30 and 31.
– make the burner connections according to the wiring diagram
shown in this manual.
N L
230 V - 50 Hz
KEY:
L
N
TA
MIQ1-MIQ2 Terminals inside panel
CTP

Electrical connections

L
N
1
2
3
... 18 19 20 21 22 23
L
N 24 25 26 27 28 29 30 31 32 33
2
CTP
5
Line / Live
Neutral
Room thermostat
Programmer timer-controlled thermostat
EN
3
Fig. 35
MIQ2
TA
MIQ1
1
3
Fig. 36