2 GENERAL INTRODUCTION
These units are used for both heating and cooling applications and domestic hot water tanks.They can be combined with fan
coil units, floor heating applications, low temperature high efficiency radiators, domestic hot water tanks and solar kits, which
are all field supplied.
A wired controller is supplied with the unit .
If you choose the built-in backup heater unit, the backup heater can increase the heating capacity during cold outdoor
temperature. The backup heater also serves as a backup in case of malfunctioning and for frozen protection of the outside
water piping during winter time.
Capacity/Load
③
②
Tbivalent
① Heat pump capacity.
② Required heating capacity (site dependent).
③ Additional heating capacity provided by backup heater.
Domestic hot water tank (field supply)
A domestic hot water tank(with or without booster
heater) can be connected to the unit.
The requirement of the tank is different for different
unit and material of heat exchanger.
Tank
Temperature
probe(T5)
Coil
The booster heater should be installed below the
temperature probe (T5).
The heat exchanger (coil) should be installed below the
temperature probe.
The pipe length between the outdoor unit and tank
should be less than 5 meters.
Heat
①
exchange
C
Outdoor temperature
Room thermostat(field supplied)
Room thermostat can be connected to the unit(room
thermostat should be kept away from heating source
when selecting the installation place).
Solar kit for domestic hot water tank(field supplied)
An optional solar kit can be connected to the unit.
Operation range
Outlet
Outlet water (Heating mode)
Outlet water (Cooling mode)
Domestic hot water
Ambient temperature
Water pressure
Tank booster heater
(TBH)
Inlet
Water flow
The unit have a freeze prevention function that uses
the heat pump or backup heater to keep the water
system safe from freezing in all conditions. Since a
power failure may happen when the unit is unattended,
It's suggested to use anti-freezing flow switch in the
water system. (Refer to 9.4"Water piping").
05
Model
Volume of tank/L
Recommended
Heat exchange area/m
2
Minimum
(Stainless steel coil)
Heat exchange area/m
2
Minimum
(Enamel coil)
4kW
6kW
8kW
10kW
12kW
14kW
16kW
4~6kW 8~10kW
12~16kW
100~250
150~300
200~500
1.4
1.4
1.6
2.0
2.0
2.5
+12 ~ +65℃
+5 ~ +25℃
+12 ~ +60℃
-25 ~ +43℃
0.1~0.3MPa(g)
3
0.40~0.85m
/h
0.40~1.25m
3
/h
0.40~1.65m
3
/h
0.40~2.00m
3
/h
3
0.70~2.50m
/h
3
0.70~2.75m
/h
3
0.70~3.00m
/h