1.4
OPERATING DIAGRAM (fig. 2)
LEGEND
1 Cascade delivery probe (SMC)
2 Hydraulic compensator
3 Ankle boot ISPESL
A - Thermometer 0-120 ° C
B - 0-10 bar pressure gauge with tap
C - Maximum safety pressure switch 4 bar
D - Manual reset safety thermostat 100 ° C
E - Safety valve 4.5 bar
F - Minuma safety pressure switch 0.9 bar
4 Comdense manifold
5 Condensate drain siphon
6 Gas valve
7 Fan
8 Return probe
9 Heating sensor (SM)
10 Safety thermostat 100 ° C
11 Flue gas probe (SF)
12 Primary exchanger
42
13 Automatic vent
14 High efficiency system pump
15 Water pressure transducer
16 Check valve
17 Safety valve 5 bar
18 Return manifold
19 Gas manifold
20 Delivery manifold
21 3-way valve Ø 1 1/4 "
22 8 liter expansion vessel
23 Gas cock
ATTACKS
M System delivery
R System return
G Gas
S3 Condensate drain
Fig. 2

Publicidad