ENGLISH
Parameter programming
To enter programming mode:
• Press simoultaneously the SPEED - MODE - FUNCTION buttons.
• LED 5 turns on white.
• Press the buttons in the following sequence: SPEED - SPEED - MODE - FUNCTION - FUNCTION – MODE.
To set the relative humidity threshold (HR%):
• Press the SPEED button.
• The current threshold setting is displayed by the LED's. LED 1 60%, LED 2 75% & LED 3 90% (default setting
75%).
• Press SPEED button to modify the threshold value.
• Press the FUNCTION button to confirm.
• All the speed LEDs from 1 to 5 will blink briefly to indicate that the value has been stored and the device will
return to normal operation.
• If you do not press the FUNCTION button within 20 sec, the device will return to normal operation without
storing any changes.
To select cycle time:
• Press the MODE button.
• The current time setting is displayed by the LED's. LED 1 50sec, LED 2 60sec & LED 3 90sec (default setting
60sec).
• Press the SPEED button to change the value.
• Press the FUNCTION button to confirm.
• All the speed LEDs from 1 to 5 will flash briefly to indicate successful storage and the device will return to
normal operation.
• If the FUNCTION button is not pressed within 20 sec, the device will return to normal operation without
memorizing.
NOTE: Cycle time programming can only be carried out on the unit set as master.
To select the clogged filter alarm interval:
• Press the FUNCTION button.
• The current time interval is displayed by the LED's. LED 1 90, LED 2 180 & LED 3 365 days.
• Press the SPEED button to modify the value.
• Press the FUNCTION button to confirm.
• All the speed LEDs from 1 to 5 will blink briefly to indicate that the storage has taken place and the equipment
will return to normal operation.
• If the FUNCTION key is not pressed within 20 sec, the device will return to normal operation without
memorizing.
To reset the clogged filter counter:
• Press the SPEED - MODE - FUNCTION buttons simultaneously.
• Press the buttons in the following sequence: MODE - MODE - SPEED - SPEED - MODE - MODE.
• Press the Function key within 20 sec.
• All the speed LEDs from 1 to 5 will blink briefly to indicate that the reset has taken place and the device will
return to normal operation.
• If the FUNCTION button is not pressed within 20 sec, the device will return to normal operation without having
reset the filter timer.
Note: for regular operation between multiple devices, it is necessary to set the type of unit
!
(Master / Slave and Even / Odd)