Toshiba Carrier MMC-UP0181HP-UL Manual De Instalación página 20

Publicidad

Idiomas disponibles

Idiomas disponibles

3
Press [ 
 ] to black highlight the item code
(DN), and then press [ 
 ] and [ 
the item code
4
Press [ 
 ] to black highlight the data, and
then press [ 
 ] and [ 
 ] to set the data
5
After finishing setting the data of the item
code (DN), press [ 
Set/Fix]
"Continue?" is displayed.
6
To set the data of other item codes (DN),
press [ 
Set/Fix]
To not do other settings, press [ 
The changes are fixed, and the "Field setting
menu" screen returns.
"   " appears while data is changing.
When doing group connections:
Press [ 
Return] to open the unit selection
screen. In the unit selection screen, press
[ 
Return] to briefly display "   ", and then
return to the "Field setting menu" screen.
37-EN
Installing indoor unit on high
 ] to set
ceiling
When the height of the ceiling to be installed exceeds
11.5' (3.5 m), adjustment of air volume is necessary.
Set up the high ceiling.
Set according to the basic operation procedure
1
2
3
4
5
6
(
).
CODE No. in Procedure specifi es [5d].
Select [SET DATA] in Procedure from "List of
installable ceiling height" in this Manual.
3
For the CODE No. in Procedure
4
For the CODE No. in Procedure
Return]
SET DATA of ceiling height to be set up from the table
on the below.
UP018 to
Model MMC-
UP030
Standard
Up to
(Factory default)
11.5' (3.5 m)
11.5' (3.5 m)
Up to
High ceiling (1)
13.1' (4.0 m)
14.1' (4.3 m)
Remote controller-less setting
Change the high-ceiling setting with the DIP switch on
the indoor unit P.C. Board.
* Once the setting is changed, setting to 0003 is
possible, however setting to 0000 requires a
setting data change to 0000 using the wired remote
controller (separately sold) with the normal switch
setting (factory default).
SW501-2
SW501-1
MCU(IC501)
SET DATA
SW501-1
0000
OFF
(Factory default)
0003
OFF
To restore the factory defaults
To return the DIP switch settings to the factory
defaults, set SW501-1 and SW501-2 to OFF, connect
a separately sold wired remote controller, and then set
the data of CODE No. [5d] to "0000".
– 19 –
Filter sign setting
According to the installation condition, the fi lter sign
term (Notifi cation of fi lter cleaning) can be changed.
Follow to the basic operation procedure
1
2
3
(
For the CODE No. in Procedure
For the [SET DATA] in Procedure
SET DATA of filter sign term from the following table.
SET DATA
0000
, specify [5d].
0001
, select the
0002
0003
UP036 to
SET
0004
UP048
DATA
Up to
0000
Up to
To secure better effect of
0003
heating
When it is diffi cult to obtain satisfactory heating due
to installation place of the indoor unit or structure of
the room, the detection temperature of heating can be
raised. Also use a circulator or other device to circulate
heat air near the ceiling.
Follow to the basic operation procedure
1
2
3
(
For the CODE No. in Procedure
For the set data in Procedure
SET DATA of shift value of detection temperature to
be set up from the following table.
SET DATA
0000
0001
0002
0003
0004
0005
0006
SW501-2
OFF
ON
Changing the wind direction
Up / down direction: Horizontal louvres
4
5
6
).
3
, specify [01].
4
, select the
Filter sign term
None
150H
2500H
(Factory default)
5000H
10000H
* Display while swinging
1
Press [ 
"Wind direction" screen (horizontal louvres)
2
Press [ 
direction
4
5
6
).
3
, specify [06].
(1)
4
, select the
Detection temperature shift value
Heat, Fan, Auto (Heat)
No shift
Cool, Dry, Auto (Cool)
1.8 °F (+1 °C)
3.6 °F (+2 °C)
(Factory default)
5.4 °F (+3 °C)
7.2 °F (+4 °C)
9.0 °F (+5 °C)
10.8 °F (+6 °C)
 ] and [ 
 ] to switch to the
 ] and [ 
 ] to select wind
(2)
(3)
(4)
(5)
Swing
Operation mode
Settable angles
(1), (2), (3), (4), (5), Swing
(1), (2), (3), Swing
38-EN