Installation space
Reserve suffi cient space required for installation or service work.
9.8" (250)
or more
Ceiling height
Model MMC-
Possible installed ceiling height
UP018 to UP030
Up to 13'1" (4.0 m)
UP036 to UP048
Up to 14'1" (4.3 m)
If height of ceiling exceeds 11'6" (3.5 m), hot air becomes difficult to reach the floor surface, and then the change of
setup of high ceiling is necessary.
For the change method of high ceiling, refer to the application control, "Installing indoor unit on high ceiling" in this
Manual.
Maximum installation height
Model MMC-
UP018 to UP030
Standard (Factory default)
Up to 11'6" (3.5 m)
High ceiling (1)
Up to 13'1" (4.0 m)
The lighting time of the fi lter sign (notifi cation of fi lter cleaning) on the remote controller can be changed according
to installation conditions.
When it is diffi cult to obtain satisfactory heating due to location place of the indoor unit or the structure of the room,
the detection temperature of heating can be raised.
For change the setup time, refer to the application control, "Filter sign setting" and "To secure better effect of
heating" in this Manual.
In case of wireless type
Decide the position which remote controller is operated and the installation place.
And then refer to the Installation Manual of the wireless remote controller kit sold separately.
(The signal of the wireless type remote controller can be received within approx. 26'3" (8 m).
This distance is a criterion and varies a little according to capacity of the battery)
To prevent malfunction, select a place where is not affected by a fl uorescent lamp or direct sunlight.
Two wireless-type indoor units can be set in a room.
15-EN
(Unit: in (mm))
9.8" (250)
or more
UP036 to UP048
SET DATA
Up to 11'6" (3.5 m)
0000
Up to 14'1" (4.3 m)
0003
4
Installation
CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering
cloth or other material to not damage the unit.
Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specifi ed.
To install vibration isolation material to hanging bolts, confi rm that it does not increase the unit vibration.
External dimensions
Upper pipe draw-out port (knockout hole)
Power supply wire take-in port
3.4"
(knockout hole Ø1.6" (40))
(87)
Left drain pipe connecting port
Refrigerant pipe connecting port
G (Liquid side)
Refrigerant pipe connecting port
H (Gas side)
B (Hanging position)
A
Signal receiving unit mounting section
– 8 –
(Unit: in (mm))
8.6"
(218)
2.6"
9.3" (235)
4.3" (109)
(66)
4.1" (102)
5.2" (132)
Drain pipe connecting port
7.6" (192)
Outer diameter 1.1" (27)
3.9"
(98)
C
6.3" (158)
Remote controller wire take-in port
F
Remote controller wire take-in
D
port (Knockout hole)
E
Power supply wire take-in port
(knockout hole Ø1.6" (40))
Air taking-in port
Left drain pipe draw-out port
(Duct sold separately)
(knockout hole)
(Knockout hole Ø3.6" (92))
Model
A
B
C
D
E
MMC-
37.4"
35.7"
12.9"
10.7"
13.9"
UP018
(950)
(906)
(328)
(270)
(353)
UP024 to
50.0"
48.2"
12.9"
10.7"
13.9"
UP030
(1270)
(1223)
(328)
(270)
(353)
UP036 to
62.5"
60.7"
13.7"
12.0"
14.9"
UP048
(1586)
(1540)
(348)
(303)
(378)
3.5" (87)
F
G
H
12.4"
Ø1/4"
Ø1/2"
(313)
(6.4)
(12.7)
12.4"
Ø3/8"
Ø5/8"
(313)
(9.5)
(15.9)
EN
13.2"
Ø3/8"
Ø5/8"
(333)
(9.5)
(15.9)
FR
ES