Descargar Imprimir esta página

Toshiba Carrier MMD-UP0241HP-UL Manual De Instalación página 23

Publicidad

Idiomas disponibles

Idiomas disponibles

External static pressure
settings
<Change on wired remote controller>
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
1
2
3
4
5
6
procedure (
).
Specify [5d] to the CODE No. in procedure
4
For the SET DATA of procedure
, select a
SET DATA of the external static pressure to be set
up from the following table.
SET DATA
External static pressure
0000
0.80 in.WG
Factory default
0001
0.40 in.WG
0002
0.32 in.WG
0003
0.68 in.WG
0004
0.60 in.WG
0005
0.20 in.WG
0006
1.00 in.WG
The list above is when SW501-1 and SW501-2 is OFF.
If the setting is wrong, "P12" may appear indicating a
fan motor error.
<Setting up on the circuit board of the indoor unit>
To set up the external static pressure, use the DIP switch on the circuit board of the wireless reception part.
For details, refer to the instruction manual of the wireless remote controller kit. Alternatively, use the switch on the
indoor micro computer circuit board as shown in the following figure and table.
43-EN
3
.
SW501-1
OFF
ON
OFF
SW501-2
OFF
OFF
ON
Factory
SET DATA
0001
0003
default
To reset to the factory default
Switch off SW501-1 and SW501-2, connect a separately-sold
wired remote controller, and then perform the procedure for
external static pressure settings on this page to set the [5d] data
to "0000".
Filter sign setting
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
1
2
3
4
5
(
For the CODE No. in Procedure
For the [SET DATA] in Procedure
SET DATA of filter sign term from the following table.
SET DATA
Filter sign term
0000
0001
0002
(Factory default)
0003
0004
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other device to circulate
heat air near the ceiling.
Follow to the basic operation procedure
1
2
3
4
5
(
For the CODE No. in Procedure
For the SET DATA in Procedure
SET DATA of shift value of detection temperature
to be set up from the following table.
ON
SET DATA
Detection temperature shift value
ON
0000
0006
0001
0002
(Factory default)
0003
0004
0005
0006
+10.8 °F (+6 °C)
– 22 –
Group control
In a group control, a remote controller can control
up to maximum 8 or 16 units. (Depending on the
outdoor unit.)
6
The wired remote controller only can control a group
).
3
control. The wireless remote controller is unavailable
, specify [01].
for this control.
4
, select the
For wiring procedure and wires of the individual line
(Identical refrigerant line) system, refer to "Electrical
Connection" in this Manual.
None
Wiring between indoor units in a group is performed
in the following procedure.
150 H
Connect the indoor units by connecting the remote
2500 H
controller wires from the remote controller terminal
blocks (A, B) of the indoor unit connected with a
5000 H
remote controller to the remote controller terminal
10000 H
blocks (A, B) of the other indoor unit. (Non-polarity)
For address setup, refer to the Installation Manual
attached to the outdoor unit.
Remote controller sensor
The temperature sensor of the indoor unit senses
room temperature usually. Set the remote controller
sensor to sense the temperature around the remote
controller.
Select items following the basic operation procedure
1
2
3
4
(
6
).
• Specify [32] for the CODE No. in Procedure
3
, specify [06].
• Select the following data for the SET DATA in
4
, select the
4
Procedure
.
SET DATA
Remote controller
sensor
No shift
+1.8 °F (+1 °C)
When
flashes, the remote contr oller sensor is
+3.6 °F (+2 °C)
defective.
Select the SET DATA [0000] (not used) or replace the
+5.4 °F (+3 °C)
remote controller.
+7.2 °F (+4 °C)
+9 °F (+5 °C)
5
6
).
3
.
0000
0001
Not used
Used
(factory default)
EN
FR
ES
44-EN

Publicidad

loading

Este manual también es adecuado para:

Mmd-up0301hp-ulMmd-up0361hp-ulMmd-up0481hp-ulMmd-up0541hp-ul