5. Installation / 6. Commissioning / Electrical connections

5. Installation

Protect measuring instruments from contamination, high tempera-
ture changes and vibrations
GB
In order to avoid any additional heating, the instruments must not be
exposed to direct solar irradiation while in operation.
The differential pressure transmitter must be screw-fitted on a
suitable vertical surface. The instrument has to be mounted horizon-
tally using the enclosed mounting screws.

6. Commissioning / Electrical connections

Output signal
DC 0 ... 10 V, 3-wire
optionally 4 ... 20 mA, 2-wire

Supply voltage

DC 13 ... 32 V
Electrical connection
PG-gland M16
Screw terminals max. 1.5 mm²

Connection diagram

Output signal DC 0 ... 10 V, 3-wire
Uv Out Gnd
6
Uv
Out
Gnd
Legend
Pin 1: Power supply (+)
Pin 2: Output signal
Pin 3: Ground
WIKA operating instructions air2guide model A2G-55
Output signal 4 ... 20 mA, 2-wire
Loop
Legend
Pin 1: Loop +
Pin 3: Loop -