II.3.1.3
Check compressor oil level sensor
Was pre-heating ac tivated at least 24 hours before s tart-up?
The compressor is r ead y for start-up
II.3.1.4
Check hydraulic connections
Have the water connections been made to a professional
Is the water inlet/outlet direction correct?
Are the circuits full of water and have the pipes been bled of
Does the water flow c onform to what is stated in the user
Do the pumps turn in the right direction?
Are the flow meters (if installed) acti ve and correctl y
Are the water filters placed upstream from the evaporator
and recovery unit in good wor king order and c orrectl y
The water connections ar e compliant
START
ª
Is the oil level sufficient?
ª
YES
ª
YES
START
ª
standard?
ª
YES
ª
YES
any air residue?
ª
YES
manual ?
ª
YES
ª
YES
connected?
ª
YES
installed?
ª
YES
SECTION II: INST ALL ATION AND MAINTEN ANCE
¨
¨
Top up as necess ary
NO
¨
¨
NO
Activate pre-heati ng and wait 24 hours.
¨
¨
Bring the c onnections up to standard.
NO
¨
¨
Correct the inlet/outlet direction.
NO
¨
¨
Fill the circuits and/or bleed the air.
NO
¨
¨
NO
Correct the water flow rate.
¨
¨
NO
Correct the rotation direction.
¨
¨
Repair or replace the component.
NO
¨
¨
NO
Repair or replace the component.
68