Descargar Imprimir esta página

Hitachi YUTAKI S Serie Manual De Instalación Y Funcionamiento página 33

Ocultar thumbs Ver también para YUTAKI S Serie:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 39
ELECTRICAL WIRING
12.4. WIRES SIZE
■ Field Minimum Wire Sizes for Power Source
Model
RAS-8HRNME-AF
RAS-10HRNME-AF
NOTES:
1. Follow local codes and regulations when selecting field wires.
2. The above wire sizes marked with
Standard, EN60 335-1. Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord
(code designation H05RN-F).
3. The above wire sizes marked with
(Flame Retardant Polyflex Wire) manufactured by HITACHI Cable Ltd. Japan.
4. In the case that the power cables are connected in series, add each unit maximum current and select wires below.
5. The earth cable size complied with local code: IEC 245, No. 571.
CAUTION :
Use shielded wires for transmission wires between the indoor and the outdoor units, and connect the shielded part to the
earth screw in the electrical box of the indoor unit as shown below.
Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord (code designation H05RN-F)
■ Select the main switches in according to the next table:
Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord (code designation H05RN-F)
Model
RAS-8HRNME-AF
RAS-10HRNME-AF
ELB: Earthleakage Breaker; CB: Circuit Breaker
Power Source
Max. Current
13.2 A
400V/3 /50Hz
17.1 A
u
are selected at the maximum current of the unit according to the European
v
are selected at the maximum current of the unit according to the wire, MLFC
Power Source
400V/3 /50Hz
Power Source Cable Size
u
EN60 335-1
2.5 mm²
4.0 mm²
Max. Current
CB
13.2 A
20 A
17.1 A
30 A
Transmitting Cable Size
v
u
MLFC
EN60 335-1
1.25 mm²
0.75 mm²
2.0 mm²
ELB
no. poles/A/mA
4/20/30
4/30/30
PMML0215A rev.1 - 02/2012
v
MLFC
0.75 mm²
35

Publicidad

loading