10 EN – Quick installation guide (North America)
5. Measure that the installation is de-energized.
Use a multimeter with an impedance of at least 1 Mohm.
Make sure that the voltage between the drive module input power terminals
(L1/U1, L2/V1, L3/W1) and the grounding (PE) busbar is close to 0 V.
Make sure that the voltage between the drive module UDC+ and UDC- terminals
and the grounding (PE) busbar is close to 0 V.
6. Install temporary grounding as required by the local regulations.
7. Ask the person in control of the electrical installation work for a permit to work.
USA
Select the power cables
Size the power cables according to local regulations to carry the nominal current given on
USA
the type designation label of your drive.
Ensure the cooling
DE
See the table on page
operating temperature range of the drive without derating is -15 to +40 °C.
ES
For more information, see ACS580-04 drive modules hardware manual
(3AXD50000015497 [English]).
FI
Protect the drive and input power cables
FR
See
Fuses (UL)
Install the drive module in a cabinet
IT
See figure
B
on page 97:
Install the punched section to the back of the cabinet frame.
NL
Remove the pedestal guide plate from the bottom of the drive module.
Install the support rails and pedestal guide plate to the cabinet bottom frame.
PL
Install the telescopic insertion/extraction ramp to the pedestal guide plate.
Option +B051: See figure
PT
Remove the sheeting from the clear plastic shrouds from both sides.
See figure
D
on page 97:
Install the fastening bracket to the drive module.
RU
Option +B051:
Install the bottom grille to the drive module if there is no bottom plate in the cabinet
SV
and degree of protection of IP20 is needed for the drive module from the bottom
side.
TR
Install the top metallic shroud to the drive module.
Install the back shrouds to the drive module.
ZH
See figure
E
on page 97:
Attach the drive module to the cabinet frame with chains.
Push the drive module into the cabinet along the telescopic insertion/extraction ramp.
Remove the ramp.
96
for the losses and cooling air flow through the drive. The allowed
on page
95
for branch circuit protection per NEC. Obey local regulations.
C
on page 97: