Connect the control cables
See figure
X
on page 100.
1. Ground the outer shields of all external control cables 360 degrees at the cabinet
entry.
2. Ground the pair-cable shields of external control cables to a grounding clamp below
the control unit. Leave the other end of the shields unconnected or ground them
indirectly via a high-frequency capacitor with a few nanofarads, eg, 3.3 nF / 630 V.
3. Connect the conductors to the appropriate terminals of the control unit. See page 14.
4. Wire the option modules if included in the delivery.