4 EN – Quick installation guide (IEC)
5. Measure that the installation is de-energized.
Use a multimeter with an impedance of at least 1 Mohm.
Make sure that the voltage between the drive module input power terminals
(L1/U1, L2/V1, L3/W1) and the grounding (PE) busbar is close to 0 V.
Make sure that the voltage between the drive module UDC+ and UDC- terminals
and the grounding (PE) busbar is close to 0 V.
6. Install temporary grounding as required by the local regulations.
EN
7. Ask the person in control of the electrical installation work for a permit to work.
DA
Select the power cables
Size the power cables according to local regulations to carry the nominal current given on
DE
the type designation label of your drive.
Ensure the cooling
ES
See the table on page
allowed operating temperature range of the drive without derating is -15 to +40 °C. For
FI
more information, see the hardware manual.
Protect the drive and input power cables
FR
See
Fuses (IEC)
power cable or drive.
IT
Install the drive module in a cabinet
NL
See figure
B
on page 97:
Install the punched section to the back of the cabinet frame.
Install the support rails and pedestal guide plate to the cabinet bottom frame.
PL
Install the telescopic insertion/extraction ramp to the pedestal guide plate.
Option +B051: See figure
PT
Remove the sheeting from the clear plastic shrouds from both sides.
See figure
D
on page 97:
RU
Install the fastening bracket to the drive module.
Option +B051:
SV
Install the bottom grille to the drive module if there is no bottom plate in the cabinet
and degree of protection of IP20 is needed for the drive module from the bottom
side.
TR
Install the top metallic shroud to the drive module.
Install the back shrouds to the drive module.
ZH
See figure
E
on page 97:
To prevent the drive module from falling, attach its lifting lugs with chains to the cabinet
frame.
Push the drive module into the cabinet along the telescopic insertion/extraction ramp.
Remove the ramp.
96
for the losses and the cooling air flow through the drive. The
on page
95
for aR fuses for protection against short-circuit in the input
C
on page 97: