Descargar Imprimir esta página

LiftMaster JDC Manual Del Usuario página 49

Publicidad

Idiomas disponibles

Idiomas disponibles

Troubleshooting (continued)
Symptom
Door runs slowly/at
half speed
Operator turns off
despite backup
battery being
connected
Operator runs
momentarily then
stops in limit learn
mode
Possible Causes Diagnosis
Wall control
If communications to the wall
disconnected or
control is absent, system will run at
damaged
half speed.
Dead or worn
Low battery voltage
batteries
Blown battery
Visually inspect battery fuses or
fuses on main
check continuity
board
Encoder wiring
Inspect encoder cable for
fault
disconnection, bad connection, cut
cable, etc.
Encoder fault or
Go to limit learn process. Number
encoder interface
displayed while in door limit learn
fault
mode is the encoder position.
Jog door several inches in either
direction and release button.
Number displayed should change.
Make sure to cancel changes or set
limit again when finished.
49
Resolution
LCD Wall control is strongly
recommended to be connected.
If it is desired to run the system
without a wall control, temporarily
or permanently, the system can be
returned to full speed operation by
replacing the wall control wiring with
a jumper wire.
If the wall control is present but not
functioning, see 'LCD wall control is
off or not functioning'
Allow batteries to recharge
Replace worn out batteries.
Batteries must both be replaced
together. Do not mix old and new
batteries.
If fuses are blown, replace both
fuses together
Correct any issues found with
encoder wiring
If encoder position does not change
with door movement, the encoder,
encoder wiring, and powerhead
main board are suspect. Check all
three for any visible damage.
Attempt power cycling and restoring
factory defaults.
Replace or repair suspected faulty
components.

Publicidad

loading