Example device
15
Optional
92 of 449
5 Installation at Site
a)
PE
K 1
9
Fig. 11: Wiring of the electrode relay: a) Connection diagram, b) Position of the
electrode in the motor housing
An electrode (B2) fitted inside the motor monitors the winding space for leakage.
The electrode is intended for connection to an electrode relay (core marking 9).
Tripping of the electrode relay must result in the pump set cutting out.
Every time the relay trips the pump set, the pump set needs to be inspected and its
insulation resistance measured.
The electrode relay (K1) must trip the motor at a tripping resistance between 3 and
60 kΩ.
▪ Télémécanique RM4-LG01
5.4.2 Connection to power supply
DANGER
Electrical connection work by unqualified personnel
Danger of death from electric shock and explosion!
▷ Always have the electrical connections installed by an electrically qualified
person.
▷ Observe regulations IEC 60364 and, for explosion-proof versions, EN 60079 .
WARNING
Incorrect connection to the mains
Damage to the power supply network, short circuit!
▷ Observe the technical specifications of the local energy supply companies.
CAUTION
Improper routing of electric cables
Damage to the power cables!
▷ Never move the power cables at temperatures below -13 °F [-25 °C].
▷ Never kink or crush the power cables.
▷ Never lift the pump set by the power cables.
▷ Adjust the length of the power cables to the site requirements.
Sanipump VX 65/80